Disinfection / Worked example

RED from a Log-Linear Biodosimetry Test

Derive a 42 mJ/cm² reduction equivalent dose from measured log inactivation and a bench dose-response slope.

Inputs

Reactor & water
gpm
gal
%
cm
cm
mJ/cm²
Lamp & quartz sleeve
mW/cm²
%
%
W
Biodosimetry (optional)
Both zero leaves RED blank
log/(mJ/cm²)

Results

US customary
Modeled UV dose
42.589 mJ/cm²
Mean exposure
5.1429 s
Lamps for model target
4
Power for model target
1.3 kW
Annular UV intensityLive diagram
Annular UV intensityRadial intensity drops with distance from the quartz sleeve. Annular cross-sectionRelative intensityUVT 92 %10Sleeve3 cmNew lampDerated42.589 mJ/cm²
Radial intensity drops with distance from the quartz sleeve.
Biodosimetry RED
42 mJ/cm²
Derated annular mean
8.2811 mW/cm²
Absorption coefficient
0.083382 cm⁻¹
Sleeve × EOLL factor
72 %
Water-gap transmission
77.869 %
Installed lamp power
1.3 kW

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. Divide the 2.1-log challenge result by the calibrated slope of 0.05 log per mJ/cm². The RED is 42 mJ/cm².
  2. Independently, the optical dose model gives about 42.59 mJ/cm² at the entered parameters. Regulatory credit depends on the validated result and applicable factors.

More worked examples

Equations & conventions

Water attenuation
α = −ln(UVT/100) / 1 cm, I(x)/I₀ = r₀/(r₀+x) × e^(−αx)

Use UVT at 254 nm over a 1 cm cell. The model assumes a cylindrical lamp, uniform water and a representative annular gap.

Annular mean and exposure
Ī = I₀ × [2r₀/(2r₀+L)] × [1−e^(−αL)]/(αL) × sleeve × EOLL × N

The absorption term tends to one at 100% UVT. Exposure is illuminated volume divided by flow, in seconds. Modeled dose is Ī × exposure in mJ/cm².

Planning lamp count
Nneeded = ceil(target / dose per lamp), kW = Nneeded × W / 1,000

The model holds hydraulic exposure and the independent contribution per lamp fixed. Use clean, new-lamp sleeve-interface intensity before the entered fouling and aging factors.

Reduction equivalent dose
RED = observed log inactivation / calibrated bench slope

Optional test inputs require a measured reactor challenge result and a log-linear bench curve through the origin over that response range. Use the validated envelope and validation factors for regulatory credit.

Planning basis

The optical estimate assumes uniform axial flow and independent lamp contributions. Short circuiting, lamp arrangement, sensor response and the dose distribution require manufacturer validation. EPA RED comes from biodosimetry.

Questions

When is the example’s RED division applicable?

Use a bench calibration linear through zero within the measured range and data for the same challenge organism and operating conditions.