Hyperscale infrastructure case

Server BGA power-cycle coverage

Compare an eight-cycle-per-day server power profile with a 36-cycle-per-day chamber profile. The test completes 800 cycles.

Inputs

°C
°C
cycles/day
cycles/day
°C
°C
eV
FailBelow mission cycle goal
Cycle AF
4.1502×
Field cycles
3,320.16
Field years
1.13704yr
Goal coverage
47.4308%

Acceleration by test temperature swing

Thermal cycle acceleration versus test temperature swingThermal cycling · log₁₀ AF-0.8340.1041.042055.190.3125Test swing ΔT (°C)Cycle AFEntered test

The curve varies chamber swing while holding the cycle rates and peak temperatures fixed. Its y-axis is logarithmic.

Download

Detailed results

Swing term
4.954247 ×
Frequency term
0.5996637 ×
Peak-temperature term
1.396958 ×
Mission cycle goal
7,000 cycles
Remaining field cycles
3,679.842 cycles

Adjust the completed cycles to find when the model reaches the field-cycle goal. Sweep the swing only where the fatigue mechanism stays comparable.

Formula trace

  1. Swing factor = (ΔTtest / ΔTuse)ᵐThe swing ratio contributes 4.954247×.
  2. Frequency factor = (fuse / ftest)ᵠThe cycle-rate ratio contributes 0.5996637×.
  3. Peak factor = exp[(Eₐ/k)(1/Tmax,use − 1/Tmax,test)]The peak-temperature term contributes 1.396958×.
  4. Field cycles = Ntest × AF · Years = Field cycles / (365 fuse)800 test cycles give 3,320.158 field cycles at 8 cycles/day.

Model assumptions

Use exponents fitted to the joint material, package and cycling profile. Frequency is cycles per day. Setting q and Eₐ to zero gives the simple swing-power Coffin–Manson approximation.

Method and sources