Bridge ICCP at a lower current
A bridge system draws 9 A through a 1.65 Ω loop. The design requests 20% voltage headroom before tap selection.
Inputs
SI unitsUse complete loop cable resistance and an independent estimate of back-EMF. Enter a manufacturer tap to override the example tap list.
- Required DC
- 16.05 V
- Rated tap
- 24 V
- AC load
- 0.21 kVA
- Annual energy
- 1,622.28 kWh/yr
Transformer-rectifier circuit
SchematicConfirm actual nameplate taps, cable drop, supply and environmental derating before equipment selection.
Calculation details
- Total loop resistance
- 1.65 Ω
- Minimum design voltage
- 19.26 V
- Operating DC power
- 0.144 kW
- Operating AC real power
- 0.185 kW
- Operating AC apparent power
- 0.21 kVA
- DC load at tap and design current
- 0.216 kW
- AC input at tap and design current
- 0.315 kVA
- Tap headroom over operating voltage
- 49.53 %
- Tap minus design voltage
- 4.74 V
- Annual operating electricity
- 227.12 USD/yr
Inputs used
- Protection current
- 9 A
- Groundbed
- 1.1 Ω
- Structure resistance
- 0.35 Ω
- Loop cable
- 0.2 Ω
- Back-EMF
- 1.2 V
- Design multiplier
- 1.2 ×
- Selected DC tap
- —
- Rectifier efficiency
- 78 %
- Power factor
- 0.88
- Electricity tariff
- 0.14 USD/kWh
- Annual runtime
- 8,760 hr/yr
Worked calculation
Starting values · SI- Loop resistance is 1.65 Ω. Required voltage is 16.05 V before the 1.2× design multiplier.
- The design minimum is 19.26 V and the selected tap is 24 V.
- Operating load is 0.18519 kW and 0.21045 kVA. Over 8,760 hours, energy is 1,622.28462 kWh/yr.
Evaluate the next candidate tap and check nameplate efficiency at the intended load.
Method and limits
Build the DC voltage budget
Required voltage = current × (groundbed + structure + loop cable resistance) + opposing back-EMF. Multiply by the design factor for the minimum design voltage.
Check the tap and AC supply
Use the first listed tap at or above the design voltage, or enter a nameplate tap. DC kW = operating voltage × current ÷ 1,000. AC kW = DC kW ÷ efficiency. AC kVA = AC kW ÷ power factor. Rated load at the selected tap is shown separately.
Estimate running cost
AC kW × annual runtime gives kWh/yr. Multiply by the entered tariff for annual cost. Headroom is (tap − operating voltage) ÷ operating voltage.