Zero entered protection load

A disconnected test circuit is entered with zero protection current and zero back-EMF.

Inputs

SI units

Use complete loop cable resistance and an independent estimate of back-EMF. Enter a manufacturer tap to override the example tap list.

A
Ω
Ω
Ω
V
×
V Blank selects the next listed tap.
%
USD/kWh
hr/yr
Required DC
0 V
Rated tap
—
AC load
0 kVA
Annual energy
0 kWh/yr

Transformer-rectifier circuit

Schematic
Transformer-rectifier circuit (schematic, not to scale)AC supplyRectifierDC loopTransformer / rectifierOPERATING DC0 VDESIGN MINIMUM0 VSELECTED TAP—
Zero modeled DC load

Confirm the input current and loop voltage. Annual energy excludes idle and standby losses.

No modeled operating power

Calculation details

Total loop resistance
1 Ω
Minimum design voltage
0 V
Operating DC power
0 kW
Operating AC real power
0 kW
Operating AC apparent power
0 kVA
DC load at tap and design current
—
AC input at tap and design current
—
Tap headroom over operating voltage
—
Tap minus design voltage
—
Annual operating electricity
0 USD/yr

Worked calculation

Starting values · SI
  1. Loop resistance is 1 Ω. Required voltage is 0 V before the 1.25× design multiplier.
  2. The design minimum is 0 V and the selected tap is unavailable or unused.
  3. Operating load is 0 kW and 0 kVA. Over 8,760 hours, energy is 0 kWh/yr.

The idealized load and energy are zero, while a real transformer-rectifier can draw power at idle.

Method and limits

  1. Build the DC voltage budget

    Required voltage = current × (groundbed + structure + loop cable resistance) + opposing back-EMF. Multiply by the design factor for the minimum design voltage.

  2. Check the tap and AC supply

    Use the first listed tap at or above the design voltage, or enter a nameplate tap. DC kW = operating voltage × current ÷ 1,000. AC kW = DC kW ÷ efficiency. AC kVA = AC kW ÷ power factor. Rated load at the selected tap is shown separately.

  3. Estimate running cost

    AC kW × annual runtime gives kWh/yr. Multiply by the entered tariff for annual cost. Headroom is (tap − operating voltage) ÷ operating voltage.