CorrosionRateLab
Menu

Energy for seasonal ICCP service

The installation operates about 4,380 hours annually. Electricity averages 0.21 USD/kWh.

Inputs

SI units

Use complete loop cable resistance and an independent estimate of back-EMF. Enter a manufacturer tap to override the example tap list.

A
Ω
Ω
Ω
V
×
V Blank selects the next listed tap.
%
USD/kWh
hr/yr
Required DC
32.85 V
Rated tap
60 V
AC load
1.33 kVA
Annual energy
5,416.77 kWh/yr

Transformer-rectifier circuit

Schematic
Transformer-rectifier circuit (schematic, not to scale)AC supplyRectifierDC loopTransformer / rectifierOPERATING DC32.85 VDESIGN MINIMUM41.06 VSELECTED TAP60 V
Tap covers design voltage

Confirm actual nameplate taps, cable drop, supply and environmental derating before equipment selection.

Design voltage ÷ tap · limit 1.00

Calculation details

Total loop resistance
1 Ω
Minimum design voltage
41.06 V
Operating DC power
1.051 kW
Operating AC real power
1.237 kW
Operating AC apparent power
1.33 kVA
DC load at tap and design current
1.92 kW
AC input at tap and design current
2.429 kVA
Tap headroom over operating voltage
82.65 %
Tap minus design voltage
18.94 V
Annual operating electricity
1,137.52 USD/yr

Worked calculation

Starting values · SI
  1. Loop resistance is 1 Ω. Required voltage is 32.85 V before the 1.25× design multiplier.
  2. The design minimum is 41.0625 V and the selected tap is 60 V.
  3. Operating load is 1.23671 kW and 1.32979 kVA. Over 4,380 hours, energy is 5,416.77176 kWh/yr.

The energy calculation scales with run hours. Idle losses, if present, need a separate estimate.

Method and limits

  1. Build the DC voltage budget

    Required voltage = current × (groundbed + structure + loop cable resistance) + opposing back-EMF. Multiply by the design factor for the minimum design voltage.

  2. Check the tap and AC supply

    Use the first listed tap at or above the design voltage, or enter a nameplate tap. DC kW = operating voltage × current ÷ 1,000. AC kW = DC kW ÷ efficiency. AC kVA = AC kW ÷ power factor. Rated load at the selected tap is shown separately.

  3. Estimate running cost

    AC kW × annual runtime gives kWh/yr. Multiply by the entered tariff for annual cost. Headroom is (tap − operating voltage) ÷ operating voltage.