CorrosionRateLab
Menu

Voltage above the candidate tap list

A modeled high-resistance circuit calls for 190 A and 5.6 Ω total loop resistance.

Inputs

SI units

Use complete loop cable resistance and an independent estimate of back-EMF. Enter a manufacturer tap to override the example tap list.

A
Ω
Ω
Ω
V
×
V Blank selects the next listed tap.
%
USD/kWh
hr/yr
Required DC
1,064.85 V
Rated tap
—
AC load
255.941 kVA
Annual energy
2,085,101.58 kWh/yr

Transformer-rectifier circuit

Schematic
Transformer-rectifier circuit (schematic, not to scale)AC supplyRectifierDC loopTransformer / rectifierOPERATING DC1,064.85 VDESIGN MINIMUM1,331.06 VSELECTED TAP—
Custom tap required

Select a manufacturer rating that meets the design voltage and DC current under site conditions.

Design voltage exceeds available tap

Calculation details

Total loop resistance
5.6 Ω
Minimum design voltage
1,331.06 V
Operating DC power
202.321 kW
Operating AC real power
238.025 kW
Operating AC apparent power
255.941 kVA
DC load at tap and design current
—
AC input at tap and design current
—
Tap headroom over operating voltage
—
Tap minus design voltage
—
Annual operating electricity
291,914.22 USD/yr

Worked calculation

Starting values · SI
  1. Loop resistance is 5.6 Ω. Required voltage is 1,064.85 V before the 1.25× design multiplier.
  2. The design minimum is 1,331.0625 V and the selected tap is unavailable or unused.
  3. Operating load is 238.02529 kW and 255.94118 kVA. Over 8,760 hours, energy is 2,085,101.57647 kWh/yr.

No candidate tap meets the design voltage. Check the resistance assumption and obtain purpose-built equipment data where appropriate.

Method and limits

  1. Build the DC voltage budget

    Required voltage = current × (groundbed + structure + loop cable resistance) + opposing back-EMF. Multiply by the design factor for the minimum design voltage.

  2. Check the tap and AC supply

    Use the first listed tap at or above the design voltage, or enter a nameplate tap. DC kW = operating voltage × current ÷ 1,000. AC kW = DC kW ÷ efficiency. AC kVA = AC kW ÷ power factor. Rated load at the selected tap is shown separately.

  3. Estimate running cost

    AC kW × annual runtime gives kWh/yr. Multiply by the entered tariff for annual cost. Headroom is (tap − operating voltage) ÷ operating voltage.