Bridge ICCP at a lower current

A bridge system draws 9 A through a 1.65 Ω loop. The design requests 20% voltage headroom before tap selection.

Inputs

SI units

Use complete loop cable resistance and an independent estimate of back-EMF. Enter a manufacturer tap to override the example tap list.

A
Ω
Ω
Ω
V
×
V Blank selects the next listed tap.
%
USD/kWh
hr/yr
Required DC
16.05 V
Rated tap
24 V
AC load
0.21 kVA
Annual energy
1,622.28 kWh/yr

Transformer-rectifier circuit

Schematic
Transformer-rectifier circuit (schematic, not to scale)AC supplyRectifierDC loopTransformer / rectifierOPERATING DC16.05 VDESIGN MINIMUM19.26 VSELECTED TAP24 V
Tap covers design voltage

Confirm actual nameplate taps, cable drop, supply and environmental derating before equipment selection.

Design voltage ÷ tap · limit 1.00

Calculation details

Total loop resistance
1.65 Ω
Minimum design voltage
19.26 V
Operating DC power
0.144 kW
Operating AC real power
0.185 kW
Operating AC apparent power
0.21 kVA
DC load at tap and design current
0.216 kW
AC input at tap and design current
0.315 kVA
Tap headroom over operating voltage
49.53 %
Tap minus design voltage
4.74 V
Annual operating electricity
227.12 USD/yr

Worked calculation

Starting values · SI
  1. Loop resistance is 1.65 Ω. Required voltage is 16.05 V before the 1.2× design multiplier.
  2. The design minimum is 19.26 V and the selected tap is 24 V.
  3. Operating load is 0.18519 kW and 0.21045 kVA. Over 8,760 hours, energy is 1,622.28462 kWh/yr.

Evaluate the next candidate tap and check nameplate efficiency at the intended load.

Method and limits

  1. Build the DC voltage budget

    Required voltage = current × (groundbed + structure + loop cable resistance) + opposing back-EMF. Multiply by the design factor for the minimum design voltage.

  2. Check the tap and AC supply

    Use the first listed tap at or above the design voltage, or enter a nameplate tap. DC kW = operating voltage × current ÷ 1,000. AC kW = DC kW ÷ efficiency. AC kVA = AC kW ÷ power factor. Rated load at the selected tap is shown separately.

  3. Estimate running cost

    AC kW × annual runtime gives kWh/yr. Multiply by the entered tariff for annual cost. Headroom is (tap − operating voltage) ÷ operating voltage.