Energy for seasonal ICCP service
The installation operates about 4,380 hours annually. Electricity averages 0.21 USD/kWh.
Inputs
SI unitsUse complete loop cable resistance and an independent estimate of back-EMF. Enter a manufacturer tap to override the example tap list.
- Required DC
- 32.85 V
- Rated tap
- 60 V
- AC load
- 1.33 kVA
- Annual energy
- 5,416.77 kWh/yr
Transformer-rectifier circuit
SchematicConfirm actual nameplate taps, cable drop, supply and environmental derating before equipment selection.
Calculation details
- Total loop resistance
- 1 Ω
- Minimum design voltage
- 41.06 V
- Operating DC power
- 1.051 kW
- Operating AC real power
- 1.237 kW
- Operating AC apparent power
- 1.33 kVA
- DC load at tap and design current
- 1.92 kW
- AC input at tap and design current
- 2.429 kVA
- Tap headroom over operating voltage
- 82.65 %
- Tap minus design voltage
- 18.94 V
- Annual operating electricity
- 1,137.52 USD/yr
Inputs used
- Protection current
- 32 A
- Groundbed
- 0.65 Ω
- Structure resistance
- 0.2 Ω
- Loop cable
- 0.15 Ω
- Back-EMF
- 0.85 V
- Design multiplier
- 1.25 ×
- Selected DC tap
- 60 V
- Rectifier efficiency
- 85 %
- Power factor
- 0.93
- Electricity tariff
- 0.21 USD/kWh
- Annual runtime
- 4,380 hr/yr
Worked calculation
Starting values · SI- Loop resistance is 1 Ω. Required voltage is 32.85 V before the 1.25× design multiplier.
- The design minimum is 41.0625 V and the selected tap is 60 V.
- Operating load is 1.23671 kW and 1.32979 kVA. Over 4,380 hours, energy is 5,416.77176 kWh/yr.
The energy calculation scales with run hours. Idle losses, if present, need a separate estimate.
Method and limits
Build the DC voltage budget
Required voltage = current × (groundbed + structure + loop cable resistance) + opposing back-EMF. Multiply by the design factor for the minimum design voltage.
Check the tap and AC supply
Use the first listed tap at or above the design voltage, or enter a nameplate tap. DC kW = operating voltage × current ÷ 1,000. AC kW = DC kW ÷ efficiency. AC kVA = AC kW ÷ power factor. Rated load at the selected tap is shown separately.
Estimate running cost
AC kW × annual runtime gives kWh/yr. Multiply by the entered tariff for annual cost. Headroom is (tap − operating voltage) ÷ operating voltage.