PUE, DCiE, WUE & CUE calculator
Compare facility and IT energy, account for cooling, UPS and lighting overhead, and price a lower PUE target.
Engineering schematic
Facility energy boundary
Annual energy savings at target 2,190 MWh.
Inputs
Calculation details
| Measure | Value |
|---|---|
| Power usage effectiveness | 1.5 |
| Data center infrastructure efficiency | 66.67 % |
| Site water usage effectiveness | 1.484 L/kWh |
| Grid carbon usage effectiveness | 570 g CO₂e/kWh |
| Annual facility energy | 13,140 MWh |
| Annual IT energy | 8,760 MWh |
| Total annual facility overhead | 4,380 MWh |
| Cooling overhead | 2,803.2 MWh |
| UPS & distribution losses | 963.6 MWh |
| Lighting overhead | 175.2 MWh |
| Other overhead | 438 MWh |
| Annual facility energy at target | 10,950 MWh |
| Annual energy savings | 2,190 MWh |
| Annual energy cost savings | 240,900 $ |
| Annual grid emissions avoided | 832.2 t CO₂e |
Update the highlighted inputs to see the results.
Calculation method
- PUE = Efacility ÷ EIT
- DCiE = 100 ÷ PUE
- Site WUE = site water (L) ÷ IT energy (kWh)
- Grid CUE = PUE × emissions factor
Enter average kW and operating hours, or enter annual MWh from matching meters. The unassigned portion of facility overhead appears as other overhead. Target savings hold IT energy, tariff and the grid emissions factor constant.
Engineering limits
Use total annual water consumption within the site boundary for site WUE, including cooling and other uses. Grid CUE covers the electricity in the entered facility boundary. Account separately for any on-site fuel or other emissions sources when reporting total operational CUE.
Worked examples
DataCenterPUELab · Calculation sheet
PUE, DCiE, WUE & CUE calculator
Annual energy savings at target 2,190 MWh.
Inputs
- Meter basis
- Average power
- Total facility
- 1500 kW
- IT equipment
- 1000 kW
- Annual operating hours
- 8760 h
- Cooling
- 320 kW
- UPS & distribution losses
- 110 kW
- Lighting
- 20 kW
- Annual site water use
- 13000 m³
- Grid emissions factor
- 380 g/kWh
- Energy tariff
- 0.11 $/kWh
- Target PUE
- 1.25
Results
- Power usage effectiveness
- 1.5
- Data center infrastructure efficiency
- 66.67 %
- Site water usage effectiveness
- 1.484 L/kWh
- Grid carbon usage effectiveness
- 570 g CO₂e/kWh
- Annual facility energy
- 13,140 MWh
- Annual IT energy
- 8,760 MWh
- Total annual facility overhead
- 4,380 MWh
- Cooling overhead
- 2,803.2 MWh
- UPS & distribution losses
- 963.6 MWh
- Lighting overhead
- 175.2 MWh
- Other overhead
- 438 MWh
- Annual facility energy at target
- 10,950 MWh
- Annual energy savings
- 2,190 MWh
- Annual energy cost savings
- 240,900 $
- Annual grid emissions avoided
- 832.2 t CO₂e
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.