Low-carbon grid CUE comparison

A 4 MW IT facility uses a 45 g/kWh electricity factor. Evaluate a small PUE improvement against its grid emissions.

Engineering schematic

Facility energy boundary

Live
Facility energy boundary PUE 1.2. DCIE 83.3 %. SITE WUE 0.32 L/kWh. GRID CUE 54 g CO₂e/kWh. See the results table for the full readout. PUE1.2DCIE83.3%SITE WUE0.32L/kWhGRID CUE54g CO₂e/kWh Facility meter42k MWhIT equipment35k MWhFacility overhead7,008 MWhCurrent overhead / target allowance0%125% usedLimit 100%

Annual energy savings at target 1,401.6 MWh.

Inputs

Meter readings

Use facility and IT readings from the same boundary and period.

kW
kW
h
Overhead breakdown
kW
kW
kW
Water, carbon & target

For site WUE, include cooling and other water uses within the site boundary.

m³
g/kWh
$/kWh

Calculation details

MeasureValue
Power usage effectiveness1.2
Data center infrastructure efficiency83.33 %
Site water usage effectiveness0.32 L/kWh
Grid carbon usage effectiveness54 g CO₂e/kWh
Annual facility energy42,048 MWh
Annual IT energy35,040 MWh
Total annual facility overhead7,008 MWh
Cooling overhead4,380 MWh
UPS & distribution losses2,014.8 MWh
Lighting overhead332.88 MWh
Other overhead280.32 MWh
Annual facility energy at target40,646.4 MWh
Annual energy savings1,401.6 MWh
Annual energy cost savings112,128 $
Annual grid emissions avoided63.07 t CO₂e

Starting calculation

  1. Divide 42,048 MWh of facility energy by 35,040 MWh of IT energy to get 1.2 PUE.
  2. At a target PUE of 1.16, facility energy becomes 40,646.4 MWh. The annual difference is 1,401.6 MWh.

The avoided tonnes use the entered grid factor. The same energy reduction yields more avoided emissions on a higher-intensity grid.

Calculation method

  • PUE = Efacility ÷ EIT
  • DCiE = 100 ÷ PUE
  • Site WUE = site water (L) ÷ IT energy (kWh)
  • Grid CUE = PUE × emissions factor

Enter average kW and operating hours, or enter annual MWh from matching meters. The unassigned portion of facility overhead appears as other overhead. Target savings hold IT energy, tariff and the grid emissions factor constant.

Engineering limits

Use total annual water consumption within the site boundary for site WUE, including cooling and other uses. Grid CUE covers the electricity in the entered facility boundary. Account separately for any on-site fuel or other emissions sources when reporting total operational CUE.