150 kW GPU racks at 90% capture
Six 150 kW racks share a high-flow CDU. A warmer return creates a 15 K loop rise.
Engineering schematic
Secondary coolant loop
CDU flow headroom 172.5 L/min
Inputs
Calculation details
| Measure | Value |
|---|---|
| Total rack heat | 900 kW |
| Heat captured by coolant | 810 kW |
| Residual air cooling load | 90 kW |
| Coolant temperature rise | 15 K |
| Coolant specific heat | 4.18 kJ/(kg·K) |
| Coolant density | 997 kg/m³ |
| Coolant mass flow | 12.919 kg/s |
| Required secondary CDU flow | 777.45 L/min |
| Coolant flow per rack | 129.58 L/min |
| Rated flow headroom | 172.55 L/min |
| Pump hydraulic power | 2.138 kW |
| Estimated pump & drive input | 2.969 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Multiply 900 kW of rack heat by 90% capture to get 810 kW on the liquid loop.
- Divide captured heat by 4.18 kJ/(kg·K) and a 15 K rise. This gives 12.919 kg/s, or 777.45 L/min at the selected fluid density.
A high capture percentage still leaves air duty across the row. Include switch and power-supply heat in the air-side check.
Calculation method
- Qliquid = Prack × rack count × capture fraction
- Mass flow = Qliquid ÷ (cp × ΔT)
- Hydraulic kW = ΔP (kPa) × volume flow (m³/s)
The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.
Engineering limits
Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.
Related worked examples
DataCenterPUELab · Calculation sheet
150 kW GPU racks at 90% capture
CDU flow headroom 172.5 L/min
Inputs
- IT load per rack
- 150 kW
- Racks on this CDU
- 6
- Liquid heat capture
- 90 %
- Secondary coolant
- Water
- Supply temperature
- 32 °C
- Return temperature
- 47 °C
- Rated CDU flow
- 950 L/min
- Loop pressure drop
- 165 kPa
- Pump & drive efficiency
- 72 %
Results
- Total rack heat
- 900 kW
- Heat captured by coolant
- 810 kW
- Residual air cooling load
- 90 kW
- Coolant temperature rise
- 15 K
- Coolant specific heat
- 4.18 kJ/(kg·K)
- Coolant density
- 997 kg/m³
- Coolant mass flow
- 12.919 kg/s
- Required secondary CDU flow
- 777.45 L/min
- Coolant flow per rack
- 129.58 L/min
- Rated flow headroom
- 172.55 L/min
- Pump hydraulic power
- 2.138 kW
- Estimated pump & drive input
- 2.969 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.