Six 150 kW racks share a high-flow CDU. A warmer return creates a 15 K loop rise.

Engineering schematic

Secondary coolant loop

Live
Secondary coolant loop CDU FLOW 777.5 L/min. LOOP ΔT 15 K. AIR LOAD 90 kW. PUMP INPUT 2.97 kW. See the results table for the full readout. CDU FLOW777.5L/minLOOP ΔT15KAIR LOAD90kWPUMP INPUT2.97kW CDUWaterIT racks32 °C supply47 °C returnAir path90 kW90% to liquid6 racks on loopCDU flow / rated flow0%82% usedLimit 100%

CDU flow headroom 172.5 L/min

Inputs

Rack heat load
kW
%
Secondary coolant loop

Use loop pressure drop at the estimated operating flow.

°C
°C
L/min
kPa
%

Calculation details

MeasureValue
Total rack heat900 kW
Heat captured by coolant810 kW
Residual air cooling load90 kW
Coolant temperature rise15 K
Coolant specific heat4.18 kJ/(kg·K)
Coolant density997 kg/m³
Coolant mass flow12.919 kg/s
Required secondary CDU flow777.45 L/min
Coolant flow per rack129.58 L/min
Rated flow headroom172.55 L/min
Pump hydraulic power2.138 kW
Estimated pump & drive input2.969 kW

Starting calculation

  1. Multiply 900 kW of rack heat by 90% capture to get 810 kW on the liquid loop.
  2. Divide captured heat by 4.18 kJ/(kg·K) and a 15 K rise. This gives 12.919 kg/s, or 777.45 L/min at the selected fluid density.

A high capture percentage still leaves air duty across the row. Include switch and power-supply heat in the air-side check.

Calculation method

  • Qliquid = Prack × rack count × capture fraction
  • Mass flow = Qliquid ÷ (cp × ΔT)
  • Hydraulic kW = ΔP (kPa) × volume flow (m³/s)

The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.

Engineering limits

Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.