Low-carbon grid CUE comparison
A 4 MW IT facility uses a 45 g/kWh electricity factor. Evaluate a small PUE improvement against its grid emissions.
Engineering schematic
Facility energy boundary
Annual energy savings at target 1,401.6 MWh.
Inputs
Calculation details
| Measure | Value |
|---|---|
| Power usage effectiveness | 1.2 |
| Data center infrastructure efficiency | 83.33 % |
| Site water usage effectiveness | 0.32 L/kWh |
| Grid carbon usage effectiveness | 54 g CO₂e/kWh |
| Annual facility energy | 42,048 MWh |
| Annual IT energy | 35,040 MWh |
| Total annual facility overhead | 7,008 MWh |
| Cooling overhead | 4,380 MWh |
| UPS & distribution losses | 2,014.8 MWh |
| Lighting overhead | 332.88 MWh |
| Other overhead | 280.32 MWh |
| Annual facility energy at target | 40,646.4 MWh |
| Annual energy savings | 1,401.6 MWh |
| Annual energy cost savings | 112,128 $ |
| Annual grid emissions avoided | 63.07 t CO₂e |
Update the highlighted inputs to see the results.
Starting calculation
- Divide 42,048 MWh of facility energy by 35,040 MWh of IT energy to get 1.2 PUE.
- At a target PUE of 1.16, facility energy becomes 40,646.4 MWh. The annual difference is 1,401.6 MWh.
The avoided tonnes use the entered grid factor. The same energy reduction yields more avoided emissions on a higher-intensity grid.
Calculation method
- PUE = Efacility ÷ EIT
- DCiE = 100 ÷ PUE
- Site WUE = site water (L) ÷ IT energy (kWh)
- Grid CUE = PUE × emissions factor
Enter average kW and operating hours, or enter annual MWh from matching meters. The unassigned portion of facility overhead appears as other overhead. Target savings hold IT energy, tariff and the grid emissions factor constant.
Engineering limits
Use total annual water consumption within the site boundary for site WUE, including cooling and other uses. Grid CUE covers the electricity in the entered facility boundary. Account separately for any on-site fuel or other emissions sources when reporting total operational CUE.
Related worked examples
DataCenterPUELab · Calculation sheet
Low-carbon grid CUE comparison
Annual energy savings at target 1,401.6 MWh.
Inputs
- Meter basis
- Average power
- Total facility
- 4800 kW
- IT equipment
- 4000 kW
- Annual operating hours
- 8760 h
- Cooling
- 500 kW
- UPS & distribution losses
- 230 kW
- Lighting
- 38 kW
- Annual site water use
- 11200 m³
- Grid emissions factor
- 45 g/kWh
- Energy tariff
- 0.08 $/kWh
- Target PUE
- 1.16
Results
- Power usage effectiveness
- 1.2
- Data center infrastructure efficiency
- 83.33 %
- Site water usage effectiveness
- 0.32 L/kWh
- Grid carbon usage effectiveness
- 54 g CO₂e/kWh
- Annual facility energy
- 42,048 MWh
- Annual IT energy
- 35,040 MWh
- Total annual facility overhead
- 7,008 MWh
- Cooling overhead
- 4,380 MWh
- UPS & distribution losses
- 2,014.8 MWh
- Lighting overhead
- 332.88 MWh
- Other overhead
- 280.32 MWh
- Annual facility energy at target
- 40,646.4 MWh
- Annual energy savings
- 1,401.6 MWh
- Annual energy cost savings
- 112,128 $
- Annual grid emissions avoided
- 63.07 t CO₂e
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.