Warm-water heat-reuse loop

Eight 75 kW racks use a warm-water secondary loop at 36 °C supply and 54 °C return.

Engineering schematic

Secondary coolant loop

Live
Secondary coolant loop CDU FLOW 407.9 L/min. LOOP ΔT 18 K. AIR LOAD 90 kW. PUMP INPUT 1.15 kW. See the results table for the full readout. CDU FLOW407.9L/minLOOP ΔT18KAIR LOAD90kWPUMP INPUT1.15kW CDUWaterIT racks36 °C supply54 °C returnAir path90 kW85% to liquid8 racks on loopCDU flow / rated flow0%74% usedLimit 100%

CDU flow headroom 142.1 L/min

Inputs

Rack heat load
kW
%
Secondary coolant loop

Use loop pressure drop at the estimated operating flow.

°C
°C
L/min
kPa
%

Calculation details

MeasureValue
Total rack heat600 kW
Heat captured by coolant510 kW
Residual air cooling load90 kW
Coolant temperature rise18 K
Coolant specific heat4.18 kJ/(kg·K)
Coolant density997 kg/m³
Coolant mass flow6.778 kg/s
Required secondary CDU flow407.92 L/min
Coolant flow per rack50.99 L/min
Rated flow headroom142.08 L/min
Pump hydraulic power0.748 kW
Estimated pump & drive input1.151 kW

Starting calculation

  1. Multiply 600 kW of rack heat by 85% capture to get 510 kW on the liquid loop.
  2. Divide captured heat by 4.18 kJ/(kg·K) and a 18 K rise. This gives 6.778 kg/s, or 407.92 L/min at the selected fluid density.

Use the calculated return temperature to compare with the heat-recovery exchanger approach and design conditions.

Calculation method

  • Qliquid = Prack × rack count × capture fraction
  • Mass flow = Qliquid ÷ (cp × ΔT)
  • Hydraulic kW = ΔP (kPa) × volume flow (m³/s)

The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.

Engineering limits

Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.