Balanced bellows into a flare header

A balanced bellows PSV handles a volatile vapor at an outlet pressure above its critical boundary.

What to check

The example uses a supplied Kb of 0.71. The exact F₂ describes the nozzle regime while Kb accounts for the capacity correction.

Operating readout

Edit inputs ↓
API 526 letter
M
Required area
2,303.869mm²
Relief reserve
0.81%
Nozzle regime
Subcritical
Preliminary relief reserveThe selected effective area covers the entered load on the selected sizing basis.
Relief-valve nozzle and API 526 effective areaSPRING-LOADED PSVkPa(a)P₁ 937P₂ 634API 526 CAPACITYkg/h · log77200327DEFGHJKLMNPQRTORIFICE AREA USED99.2%
The stepped curve shows relief capacity at the entered conditions on a log scale. The dashed line marks the required load.
Calculated details
Selected effective area
2,322.576mm²
Screened capacity (largest if beyond T)
10,686.07kg/h
Flowing inlet pressure P₁
937.33kPa(a)
Total outlet backpressure P₂
634kPa(a)
Critical flow pressure Pcf
523.69kPa(a)
Subcritical coefficient F₂
0.78547
Nozzle C (SI)
0.025831
Nozzle C (US)
340.232
Applied Kb
0.71
Effective area method
Manufacturer Kb

Operating inputs

Relief case
bar(g)
Often the MAWP. Confirm the set pressure for this valve.
%
Applied to set pressure, before adding atmosphere.
kPa(a)
kPa(a)
Enter absolute pressure before the valve flows.
kPa
kg/h
°C
Gas and valve coefficients
kg/kmol
Use the manufacturer factor including subcritical flow at the entered total backpressure.
Default 1.0 applies without an upstream disk.

Calculation basis

Set the relieving pressures

P₁ = P_set,g(1 + overpressure) + P_atm. P₂ adds built-up pressure to the superimposed absolute pressure. The ideal-gas critical boundary is Pcf = P₁[2/(k + 1)]^(k/(k − 1)).

Apply the correct capacity equation

Critical area uses C = 0.03948√[k(2/(k + 1))^((k + 1)/(k − 1))] in SI (520 in US). Conventional subcritical area uses the exact F₂ and SI coefficient 17.9, with a critical-area floor to cover coefficient rounding. Balanced valves use a manufacturer Kb that accounts for subcritical flow and stays within the full-lift nozzle capacity.

Select effective area

Select the smallest API 526 letter with effective area at or above the calculated area. Reserve is selected area divided by required area minus one.