GasCompressLab

API 520 I · API 526

Upstream rupture disk combination

A vapor relief valve has an upstream disk with a preliminary combination factor of 0.90.

What to check

Change Kc from 0.90 to 1.00 to measure the area effect. Use the certified factor when available.

Operating readout

Edit inputs ↓
API 526 letter
M
Required area
2,051.412mm²
Relief reserve
13.22%
Nozzle regime
Critical
Preliminary relief reserveThe selected effective area covers the entered load on the selected sizing basis.
Relief-valve nozzle and API 526 effective areaSPRING-LOADED PSVkPa(a)P₁ 1050P₂ 119API 526 CAPACITYkg/h · log1.2e+5509DEFGHJKLMNPQRTORIFICE AREA USED88.3%
The stepped curve shows relief capacity at the entered conditions on a log scale. The dashed line marks the required load.
Calculated details
Selected effective area
2,322.576mm²
Screened capacity (largest if beyond T)
16,643.11kg/h
Flowing inlet pressure P₁
1,047.33kPa(a)
Total outlet backpressure P₂
119.33kPa(a)
Critical flow pressure Pcf
585.15kPa(a)
Subcritical coefficient F₂
—
Nozzle C (SI)
0.025831
Nozzle C (US)
340.232
Applied Kb
1
Effective area method
Critical C

Operating inputs

Relief case
bar(g)
Often the MAWP. Confirm the set pressure for this valve.
%
Applied to set pressure, before adding atmosphere.
kPa(a)
kPa(a)
Enter absolute pressure before the valve flows.
kPa
kg/h
°C
Gas and valve coefficients
kg/kmol
Default 1.0 applies without an upstream disk.

Calculation basis

Set the relieving pressures

P₁ = P_set,g(1 + overpressure) + P_atm. P₂ adds built-up pressure to the superimposed absolute pressure. The ideal-gas critical boundary is Pcf = P₁[2/(k + 1)]^(k/(k − 1)).

Apply the correct capacity equation

Critical area uses C = 0.03948√[k(2/(k + 1))^((k + 1)/(k − 1))] in SI (520 in US). Conventional subcritical area uses the exact F₂ and SI coefficient 17.9, with a critical-area floor to cover coefficient rounding. Balanced valves use a manufacturer Kb that accounts for subcritical flow and stays within the full-lift nozzle capacity.

Select effective area

Select the smallest API 526 letter with effective area at or above the calculated area. Reserve is selected area divided by required area minus one.

Related worked examples