GasCompressLab

API 520 I · API 526

Vapor duty beyond API 526 T

A deliberately large 310 t/h vapor load exceeds the largest single standardized orifice in the screen.

What to check

The negative reserve is relative to T. A new relief-system selection and scenario review are required.

Operating readout

Edit inputs ↓
API 526 letter
Beyond T
Required area
50,362.421mm²
Relief reserve
-66.69%
Nozzle regime
Critical
API 526 orifice undersizedRequired area exceeds the largest D–T effective area.
Relief-valve nozzle and API 526 effective areaSPRING-LOADED PSVkPa(a)P₁ 849P₂ 136API 526 CAPACITYkg/h · log1.0e+5437DEFGHJKLMNPQRTORIFICE AREA USED300%
The stepped curve shows relief capacity at the entered conditions on a log scale. The dashed line marks the required load.
Calculated details
Selected effective area
—
Screened capacity (largest if beyond T)
103,251.38kg/h
Flowing inlet pressure P₁
849.33kPa(a)
Total outlet backpressure P₂
136.33kPa(a)
Critical flow pressure Pcf
474.52kPa(a)
Subcritical coefficient F₂
—
Nozzle C (SI)
0.025831
Nozzle C (US)
340.232
Applied Kb
1
Effective area method
Critical C

Operating inputs

Relief case
bar(g)
Often the MAWP. Confirm the set pressure for this valve.
%
Applied to set pressure, before adding atmosphere.
kPa(a)
kPa(a)
Enter absolute pressure before the valve flows.
kPa
kg/h
°C
Gas and valve coefficients
kg/kmol
Default 1.0 applies without an upstream disk.

Calculation basis

Set the relieving pressures

P₁ = P_set,g(1 + overpressure) + P_atm. P₂ adds built-up pressure to the superimposed absolute pressure. The ideal-gas critical boundary is Pcf = P₁[2/(k + 1)]^(k/(k − 1)).

Apply the correct capacity equation

Critical area uses C = 0.03948√[k(2/(k + 1))^((k + 1)/(k − 1))] in SI (520 in US). Conventional subcritical area uses the exact F₂ and SI coefficient 17.9, with a critical-area floor to cover coefficient rounding. Balanced valves use a manufacturer Kb that accounts for subcritical flow and stays within the full-lift nozzle capacity.

Select effective area

Select the smallest API 526 letter with effective area at or above the calculated area. Reserve is selected area divided by required area minus one.