Relief sizing at a high-altitude plant

A vessel at a high-altitude plant uses 82 kPa local atmosphere for gauge-to-absolute conversion.

What to check

Check flowing inlet pressure and critical boundary after changing the atmospheric baseline.

Operating readout

Edit inputs ↓
API 526 letter
J
Required area
553.755mm²
Relief reserve
49.94%
Nozzle regime
Critical
Preliminary relief reserveThe selected effective area covers the entered load on the selected sizing basis.
Relief-valve nozzle and API 526 effective areaSPRING-LOADED PSVkPa(a)P₁ 790P₂ 116API 526 CAPACITYkg/h · log95400404DEFGHJKLMNPQRTORIFICE AREA USED66.7%
The stepped curve shows relief capacity at the entered conditions on a log scale. The dashed line marks the required load.
Calculated details
Selected effective area
830.321mm²
Screened capacity (largest if beyond T)
4,723.23kg/h
Flowing inlet pressure P₁
789.6kPa(a)
Total outlet backpressure P₂
116kPa(a)
Critical flow pressure Pcf
441.15kPa(a)
Subcritical coefficient F₂
—
Nozzle C (SI)
0.025831
Nozzle C (US)
340.232
Applied Kb
1
Effective area method
Critical C

Operating inputs

Relief case
bar(g)
Often the MAWP. Confirm the set pressure for this valve.
%
Applied to set pressure, before adding atmosphere.
kPa(a)
kPa(a)
Enter absolute pressure before the valve flows.
kPa
kg/h
°C
Gas and valve coefficients
kg/kmol
Default 1.0 applies without an upstream disk.

Calculation basis

Set the relieving pressures

P₁ = P_set,g(1 + overpressure) + P_atm. P₂ adds built-up pressure to the superimposed absolute pressure. The ideal-gas critical boundary is Pcf = P₁[2/(k + 1)]^(k/(k − 1)).

Apply the correct capacity equation

Critical area uses C = 0.03948√[k(2/(k + 1))^((k + 1)/(k − 1))] in SI (520 in US). Conventional subcritical area uses the exact F₂ and SI coefficient 17.9, with a critical-area floor to cover coefficient rounding. Balanced valves use a manufacturer Kb that accounts for subcritical flow and stays within the full-lift nozzle capacity.

Select effective area

Select the smallest API 526 letter with effective area at or above the calculated area. Reserve is selected area divided by required area minus one.