Balanced counterflow circulation loops

Two water-like streams have matching heat capacity rates in an ideal counterflow exchanger.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
66.667%
Heat duty
683.33kW
Hot outlet
49.333°C
Cold outlet
76.667°C
Effectiveness curveε EFFECTIVENESSCᵣ 1100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K
kW/K

Calculated results

Effectiveness
66.667 %
Actual heat duty
683.33 kW
Hot outlet
49.333 °C
Cold outlet
76.667 °C
Number of transfer units
2
Capacity ratio Cᵣ
1
Minimum capacity rate
12.5 kW/K
Maximum possible duty
1,025 kW
Difference from ideal duty
341.67 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 25 kW/K by Cₘᵢₙ of 12.5 kW/K to obtain NTU = 2.
  2. At Cᵣ = 1, the selected arrangement gives 66.667 % effectiveness and 683.33 kW actual duty.
  3. Apply the heat balance to get 49.333 °C at the hot outlet and 76.667 °C at the cold outlet.

At Cᵣ = 1 and NTU = 2, effectiveness is exactly two-thirds. The hot and cold temperature changes have equal magnitude.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.