Unmixed crossflow process cooling coil

Parallel tube circuits and divided air channels preserve the transverse temperature variation in both streams.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
71.569%
Heat duty
792.27kW
Hot outlet
49.314°C
Cold outlet
67.698°C
Effectiveness curveε EFFECTIVENESSCᵣ 0.71053100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K
kW/K

Calculated results

Effectiveness
71.569 %
Actual heat duty
792.27 kW
Hot outlet
49.314 °C
Cold outlet
67.698 °C
Number of transfer units
2.3704
Capacity ratio Cᵣ
0.71053
Minimum capacity rate
13.5 kW/K
Maximum possible duty
1,107 kW
Difference from ideal duty
314.73 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 32 kW/K by Cₘᵢₙ of 13.5 kW/K to obtain NTU = 2.3704.
  2. At Cᵣ = 0.71053, the selected arrangement gives 71.569 % effectiveness and 792.27 kW actual duty.
  3. Apply the heat balance to get 49.314 °C at the hot outlet and 67.698 °C at the cold outlet.

Read the operating point on the exact both-unmixed curve. Compare the mixed cases at fixed capacity rates.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.

Methodology and references