Unmixed crossflow process cooling coil
Parallel tube circuits and divided air channels preserve the transverse temperature variation in both streams.
Effectiveness curve
NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)
- Effectiveness
- 71.569%
- Heat duty
- 792.27kW
- Hot outlet
- 49.314°C
- Cold outlet
- 67.698°C
- Within the displayed screening checks.
Inputs
Calculated results
- Effectiveness
- 71.569 %
- Actual heat duty
- 792.27 kW
- Hot outlet
- 49.314 °C
- Cold outlet
- 67.698 °C
- Number of transfer units
- 2.3704
- Capacity ratio Cᵣ
- 0.71053
- Minimum capacity rate
- 13.5 kW/K
- Maximum possible duty
- 1,107 kW
- Difference from ideal duty
- 314.73 kW
Worked solution
Preset calculation · Metric SI
- Divide UA of 32 kW/K by Cₘᵢₙ of 13.5 kW/K to obtain NTU = 2.3704.
- At Cᵣ = 0.71053, the selected arrangement gives 71.569 % effectiveness and 792.27 kW actual duty.
- Apply the heat balance to get 49.314 °C at the hot outlet and 67.698 °C at the cold outlet.
Read the operating point on the exact both-unmixed curve. Compare the mixed cases at fixed capacity rates.
Calculation basis
Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.
Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.
Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.