HeatExchangerLab

Parallel-flow batch rinse preheater

A co-current exchanger preheats a rinse tank. The selected UA approaches the parallel-flow effectiveness ceiling.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
61.986%
Heat duty
368.19kW
Hot outlet
42.089°C
Cold outlet
41.546°C
Effectiveness curveε EFFECTIVENESSCᵣ 0.6100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K
kW/K

Calculated results

Effectiveness
61.986 %
Actual heat duty
368.19 kW
Hot outlet
42.089 °C
Cold outlet
41.546 °C
Number of transfer units
3
Capacity ratio Cᵣ
0.6
Minimum capacity rate
9 kW/K
Maximum possible duty
594 kW
Difference from ideal duty
225.81 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 27 kW/K by Cₘᵢₙ of 9 kW/K to obtain NTU = 3.
  2. At Cᵣ = 0.6, the selected arrangement gives 61.986 % effectiveness and 368.19 kW actual duty.
  3. Apply the heat balance to get 42.089 °C at the hot outlet and 41.546 °C at the cold outlet.

Increase UA and watch both outlet temperatures approach one another. The capacity ratio sets the asymptotic ceiling.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.

Methodology and references