Crossflow with both streams mixed
Mixing across the passages on both sides changes the effectiveness curve at high NTU.
Effectiveness curve
NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)
- Effectiveness
- 62.12%
- Heat duty
- 637.35kW
- Hot outlet
- 54.092°C
- Cold outlet
- 62.49°C
- Within the displayed screening checks.
Inputs
Calculated results
- Effectiveness
- 62.12 %
- Actual heat duty
- 637.35 kW
- Hot outlet
- 54.092 °C
- Cold outlet
- 62.49 °C
- Number of transfer units
- 6.3158
- Capacity ratio Cᵣ
- 0.76
- Minimum capacity rate
- 11.4 kW/K
- Maximum possible duty
- 1,026 kW
- Difference from ideal duty
- 388.65 kW
Worked solution
Preset calculation · Metric SI
- Divide UA of 72 kW/K by Cₘᵢₙ of 11.4 kW/K to obtain NTU = 6.3158.
- At Cᵣ = 0.76, the selected arrangement gives 62.12 % effectiveness and 637.35 kW actual duty.
- Apply the heat balance to get 54.092 °C at the hot outlet and 62.49 °C at the cold outlet.
Look at the whole effectiveness curve. More conductance can bring little gain or a modest decline beyond its peak for this idealized arrangement.
Calculation basis
Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.
Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.
Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.
Methodology and references