Isothermal process-side evaporator rating
A boiling process stream remains at its controlled saturation temperature while a hot-water loop supplies heat.
Effectiveness curve
NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)
- Effectiveness
- 71.724%
- Heat duty
- 919.86kW
- Hot outlet
- 59.724°C
- Cold outlet
- 47°C
- Within the displayed screening checks.
Inputs
Calculated results
- Effectiveness
- 71.724 %
- Actual heat duty
- 919.86 kW
- Hot outlet
- 59.724 °C
- Cold outlet
- 47 °C
- Number of transfer units
- 1.2632
- Capacity ratio Cᵣ
- 0
- Minimum capacity rate
- 28.5 kW/K
- Maximum possible duty
- 1,282.5 kW
- Difference from ideal duty
- 362.64 kW
Worked solution
Preset calculation · Metric SI
- Divide UA of 36 kW/K by Cₘᵢₙ of 28.5 kW/K to obtain NTU = 1.2632.
- At Cᵣ = 0, the selected arrangement gives 71.724 % effectiveness and 919.86 kW actual duty.
- Apply the heat balance to get 59.724 °C at the hot outlet and 47 °C at the cold outlet.
Cold outlet stays at 47 °C. The hot-water capacity rate alone sets Cₘᵢₙ and determines the hot outlet.
Calculation basis
Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.
Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.
Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.
Methodology and references