HeatExchangerLab

Single-shell hydrocarbon cooler rating

A one-shell-pass exchanger cools a process hydrocarbon against tempered water at a revised flow.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
62.994%
Heat duty
1,782.5kW
Hot outlet
80.477°C
Cold outlet
84.893°C
Effectiveness curveε EFFECTIVENESSCᵣ 0.64095100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K
kW/K

Calculated results

Effectiveness
62.994 %
Actual heat duty
1,782.5 kW
Hot outlet
80.477 °C
Cold outlet
84.893 °C
Number of transfer units
1.7361
Capacity ratio Cᵣ
0.64095
Minimum capacity rate
21.6 kW/K
Maximum possible duty
2,829.6 kW
Difference from ideal duty
1,047.1 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 37.5 kW/K by Cₘᵢₙ of 21.6 kW/K to obtain NTU = 1.7361.
  2. At Cᵣ = 0.64095, the selected arrangement gives 62.994 % effectiveness and 1,782.5 kW actual duty.
  3. Apply the heat balance to get 80.477 °C at the hot outlet and 84.893 °C at the cold outlet.

Read both outlet predictions. Compare duty with ideal counterflow at the same conductance and inlet condition.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.

Methodology and references