HeatExchangerLab

Crossflow with both streams mixed

Mixing across the passages on both sides changes the effectiveness curve at high NTU.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
62.12%
Heat duty
637.35kW
Hot outlet
54.092°C
Cold outlet
62.49°C
Effectiveness curveε EFFECTIVENESSCᵣ 0.76100%50%008 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K
kW/K

Calculated results

Effectiveness
62.12 %
Actual heat duty
637.35 kW
Hot outlet
54.092 °C
Cold outlet
62.49 °C
Number of transfer units
6.3158
Capacity ratio Cᵣ
0.76
Minimum capacity rate
11.4 kW/K
Maximum possible duty
1,026 kW
Difference from ideal duty
388.65 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 72 kW/K by Cₘᵢₙ of 11.4 kW/K to obtain NTU = 6.3158.
  2. At Cᵣ = 0.76, the selected arrangement gives 62.12 % effectiveness and 637.35 kW actual duty.
  3. Apply the heat balance to get 54.092 °C at the hot outlet and 62.49 °C at the cold outlet.

Look at the whole effectiveness curve. More conductance can bring little gain or a modest decline beyond its peak for this idealized arrangement.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.