HeatExchangerLab

Isothermal process-side evaporator rating

A boiling process stream remains at its controlled saturation temperature while a hot-water loop supplies heat.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
71.724%
Heat duty
919.86kW
Hot outlet
59.724°C
Cold outlet
47°C
Effectiveness curveε EFFECTIVENESSCᵣ 0100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K

Calculated results

Effectiveness
71.724 %
Actual heat duty
919.86 kW
Hot outlet
59.724 °C
Cold outlet
47 °C
Number of transfer units
1.2632
Capacity ratio Cᵣ
0
Minimum capacity rate
28.5 kW/K
Maximum possible duty
1,282.5 kW
Difference from ideal duty
362.64 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 36 kW/K by Cₘᵢₙ of 28.5 kW/K to obtain NTU = 1.2632.
  2. At Cᵣ = 0, the selected arrangement gives 71.724 % effectiveness and 919.86 kW actual duty.
  3. Apply the heat balance to get 59.724 °C at the hot outlet and 47 °C at the cold outlet.

Cold outlet stays at 47 °C. The hot-water capacity rate alone sets Cₘᵢₙ and determines the hot outlet.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.

Methodology and references