HeatExchangerLab

Plate count under a tight temperature drive

A plant heat-recovery loop targets a low corrected mean temperature difference at a multi-megawatt duty.

Chevron plate pack

Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8

Edit inputs ↓
Plate count
193
Channel speed
0.88816m/s
Wall shear
81.511Pa
Plate ΔP
254.19kPa
Chevron plate packCORRUGATED PLATESCHANNEL SECTION45° chevronShear 81.511 Pa3.8 mm gap050 Pa screen100 Pa+
Chevron angle changes the ribs. The channel gap is enlarged. The shear bar uses a 50 Pa screen and caps at 100 Pa. The channel label shows the calculated shear.
  • Within the displayed screening checks.

Inputs

kW
W/(m²·K)
K
m
m
mm
L/min
kg/m³
mPa·s

Calculated results

Installed plates
193
Channel velocity
0.88816 m/s
Average wall shear
81.511 Pa
Core pressure drop
254.19 kPa
Active thermal plates
191
Channels per side per pass
32
Hydraulic diameter
6.08 mm
Channel Reynolds number
5,794.8
Required transfer area
280.7 m²
Area per active plate
1.4813 m²
Installed transfer area
282.92 m²
Darcy friction factor
0.82831

Worked solution

Preset calculation · Metric SI

  1. Divide target duty by service U times corrected mean ΔT. The required transfer area is 280.7 m².
  2. Each active plate contributes 1.4813 m². The balanced pack uses 193 plates including the two end plates.
  3. Use 32 channels per side per pass to find velocity. The chevron model gives 81.511 Pa wall shear and 254.19 kPa core loss.

Check how plate count grows and how increasing the number of parallel passages affects liquid speed.

Calculation basis

Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.

The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.

Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.

Methodology and references