Plate count under a tight temperature drive
A plant heat-recovery loop targets a low corrected mean temperature difference at a multi-megawatt duty.
Chevron plate pack
Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8
- Plate count
- 193
- Channel speed
- 0.88816m/s
- Wall shear
- 81.511Pa
- Plate ΔP
- 254.19kPa
- Within the displayed screening checks.
Inputs
Calculated results
- Installed plates
- 193
- Channel velocity
- 0.88816 m/s
- Average wall shear
- 81.511 Pa
- Core pressure drop
- 254.19 kPa
- Active thermal plates
- 191
- Channels per side per pass
- 32
- Hydraulic diameter
- 6.08 mm
- Channel Reynolds number
- 5,794.8
- Required transfer area
- 280.7 m²
- Area per active plate
- 1.4813 m²
- Installed transfer area
- 282.92 m²
- Darcy friction factor
- 0.82831
Worked solution
Preset calculation · Metric SI
- Divide target duty by service U times corrected mean ΔT. The required transfer area is 280.7 m².
- Each active plate contributes 1.4813 m². The balanced pack uses 193 plates including the two end plates.
- Use 32 channels per side per pass to find velocity. The chevron model gives 81.511 Pa wall shear and 254.19 kPa core loss.
Check how plate count grows and how increasing the number of parallel passages affects liquid speed.
Calculation basis
Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.
The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.
Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.
Methodology and references