1,000 CFM Round Duct and Noise Check
Size a 1,000 CFM galvanized round duct and compare the effect of a 750 FPM airspeed target on its internal diameter.
Inputs
Results ↓Results
Example estimateRound internal diameter16 in
- Rectangular internal size
- 20 × 10 in
- Rectangular equivalent diameter
- 15.23 in
- Target friction
- 0.1 in. w.c./100 ft
- Round friction
- 0.046 in. w.c./100 ft
- Rectangular friction
- 0.0585 in. w.c./100 ft
- Friction-only round minimum
- 13.66 in
- Velocity-only round minimum
- 15.64 in
- Round material
- Galvanized steel
- Rectangular material
- Galvanized steel
Calculation inputs
- Design airflow
- 1000 CFM
- Duct material
- Galvanized steel
- Rectangular short side
- 10 in
- Air velocity limit
- 750 FPM
- Friction rate source
- Enter target friction rate
- Target friction rate
- 0.1 in. w.c./100 ft
Worked example
The 750 FPM velocity cap represents a noise-conscious comparison alongside a 0.10 in. w.c./100 ft target. Compare the rounded diameter against what the friction target alone would require.
Round internal diameter 16 in
What to check next
Confirm air density and airflow at the operating conditions. Check the register and abrupt fittings separately when noise near an occupied room is the main concern.
Formulas and assumptions
- Pressure budget
- Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
- Straight duct loss
- The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
- Rectangular equivalent
- Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.
Frequently asked questions
How do I calculate airspeed for 1,000 CFM in a round duct?
Divide 1,000 by the circular area in square feet. For a 16-inch internal diameter, the result is about 716 FPM.
Which diameter should I compare with a 1,000 CFM round duct catalog?
Use the clear internal diameter. Lining or insulation within the shell reduces the usable section.