Psychrometric Dew Point & Enthalpy Calculator
Find dew point, Stull wet-bulb, grains per pound and air enthalpy. Check cold-surface condensation and calculate sensible and latent BTU/h.
Inputs
Results ↓Results
Example estimate- Stull wet-bulb
- 68 °F
- Entering humidity ratio
- 85.9 gr/lb
- Entering enthalpy
- 32.17 BTU/lb dry air
- Leaving enthalpy
- 23.35 BTU/lb dry air
- Condensation at surface
- At or below dew point
- Surface margin above dew point
- -8 °F
- Sensible load
- 7,671 BTU/h
- Latent load
- 7,641 BTU/h
- Total airside load
- 15,312 BTU/h
- Sensible heat ratio
- 0.501
Calculation inputs
- Entering dry-bulb temperature
- 78 °F
- Entering relative humidity
- 60 %
- Cold surface temperature
- 55 °F
- Barometric pressure
- 101.325 kPa
- Leaving dry-bulb temperature
- 60 °F
- Leaving relative humidity
- 75 %
- Airflow at the entering condition
- 400 CFM
Worked example
Air at 78°F and 60% RH passes a 55°F duct jacket. Compare the entering dew point with that surface, then use the entering and leaving air states to find coil load.
Entering-air dew point 63 °F
Formulas and assumptions
- Moist-air state
- A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
- Enthalpy and wet-bulb
- Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
- Airside heat transfer
- Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.
Frequently asked questions
At what surface temperature does a cold duct start sweating?
A surface at or below the dew point of the air touching it can accumulate condensation. Measure the outer jacket temperature and the humidity next to it.
Why is psychrometric enthalpy expressed per pound of dry air?
The water mass changes as air is cooled or dehumidified. Using a pound of dry air as the basis keeps the reference mass consistent.
When is the Stull wet-bulb estimate less reliable?
It is a sea-level approximation covering −20°C to 50°C and about 5% to 99% RH, with reduced accuracy in very cold, dry air. Saturated air is treated as wet-bulb equal to dry-bulb.