800 CFM Rectangular Duct for an 8-Inch Cavity
Find an equal-friction rectangular duct for 800 CFM where the internal short side is limited to 8 inches.
Inputs
Results ↓Results
Example estimate- Rectangular internal size
- 19 × 8 in
- Rectangular equivalent diameter
- 13.18 in
- Target friction
- 0.08 in. w.c./100 ft
- Round friction
- 0.0587 in. w.c./100 ft
- Rectangular friction
- 0.079 in. w.c./100 ft
- Friction-only round minimum
- 13.14 in
- Velocity-only round minimum
- 13.14 in
- Round material
- Galvanized steel
- Rectangular material
- Galvanized steel
Calculation inputs
- Design airflow
- 800 CFM
- Duct material
- Galvanized steel
- Rectangular short side
- 8 in
- Air velocity limit
- 850 FPM
- Friction rate source
- Enter target friction rate
- Target friction rate
- 0.08 in. w.c./100 ft
Worked example
An 8-inch height limit may push a rectangular duct wider than expected. The result keeps the short side fixed and increases width until both the friction and velocity limits pass.
Round internal diameter 14 in
What to check next
Measure actual clear height after insulation, stiffeners and installation clearance. Compare a deeper duct using the same airflow before selecting a very wide profile.
Formulas and assumptions
- Pressure budget
- Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
- Straight duct loss
- The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
- Rectangular equivalent
- Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.
Frequently asked questions
Can I take the area of a round 800 CFM duct and flatten it?
An equal-area rectangle has a different perimeter and resistance. Check the friction-equivalent diameter and then calculate velocity from its shape.
Why would an 8-inch-high duct return no rectangular fit?
The highest allowed width is four times the short side. If the result still fails friction or velocity, increase available height or divide airflow among ducts.