800 CFM Rectangular Duct for an 8-Inch Cavity

Find an equal-friction rectangular duct for 800 CFM where the internal short side is limited to 8 inches.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

0.06–0.12 is a comparison range. Use the project’s actual friction budget.

Results

Example estimate
Round internal diameter14 in
Ø 14 in 19 × 8 in Round velocity 748 / 850 FPM Rectangular velocity 758 / 850 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
19 × 8 in
Rectangular equivalent diameter
13.18 in
Target friction
0.08 in. w.c./100 ft
Round friction
0.0587 in. w.c./100 ft
Rectangular friction
0.079 in. w.c./100 ft
Friction-only round minimum
13.14 in
Velocity-only round minimum
13.14 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

An 8-inch height limit may push a rectangular duct wider than expected. The result keeps the short side fixed and increases width until both the friction and velocity limits pass.

Round internal diameter 14 in

What to check next

Measure actual clear height after insulation, stiffeners and installation clearance. Compare a deeper duct using the same airflow before selecting a very wide profile.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

Can I take the area of a round 800 CFM duct and flatten it?

An equal-area rectangle has a different perimeter and resistance. Check the friction-equivalent diameter and then calculate velocity from its shape.

Why would an 8-inch-high duct return no rectangular fit?

The highest allowed width is four times the short side. If the result still fails friction or velocity, increase available height or divide airflow among ducts.

More sizing examples

Open the general duct sizing calculator