600 CFM Flex Duct Size and Friction

Compare a 600 CFM fully stretched flex duct against a rectangular steel option using the same pressure and velocity targets.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

0.06–0.12 is a comparison range. Use the project’s actual friction budget.

Results

Example estimate
Round internal diameter13 in
Ø 13 in 14 × 8 in Round velocity 651 / 800 FPM Rectangular velocity 771 / 800 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
14 × 8 in
Rectangular equivalent diameter
11.46 in
Target friction
0.1 in. w.c./100 ft
Round friction
0.0669 in. w.c./100 ft
Rectangular friction
0.0924 in. w.c./100 ft
Friction-only round minimum
12.03 in
Velocity-only round minimum
11.73 in
Round material
Fully stretched flex
Rectangular material
Galvanized steel
  • The flex estimate assumes a fully stretched round duct. Compression and bends can add substantial pressure loss.

Worked example

Start with a 600 CFM branch and 0.10 in. w.c./100 ft. The round option uses higher roughness for stretched flex, while the rectangular option uses galvanized steel in the same comparison.

Round internal diameter 13 in

What to check next

Check flex installation requirements for support, stretch and bend radius. Use product data for the run when compression or multiple bends are unavoidable.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

Does squeezing flex duct around a joist keep its 600 CFM rating?

A kink or compression reduces useful area and raises losses. The modeled size assumes fully stretched duct with the stated circular diameter.

Why does the rectangular 600 CFM comparison use metal?

The selected flex material represents round flexible duct. The equivalent rectangular candidate uses a separately identified galvanized construction.

More sizing examples

Open the general duct sizing calculator