Air Changes per Hour (ACH) & CFM Calculator
Convert room volume and target ACH to CFM. Compare outdoor exhaust or ERV airflow with particle CADR for rooms, homes and classrooms.
Inputs
Results ↓Results
Example estimate- Room volume
- 12,000 ft³
- Room volume in metric
- 339.8 m³
- Flow for target ACH
- 70 CFM
- Scenario outdoor baseline
- 75 CFM
- Added outdoor airflow for full ACH
- 75 CFM
- Outdoor baseline still needed
- 75 CFM
- Added particle CADR after baseline
- 0 CFM CADR
- Existing outdoor ACH
- 0 ACH
- Existing particle clean-air ACH
- 0 eACH
- The whole-dwelling example uses the 62.2 base flow before infiltration credits and other adjustments. Confirm the adopted edition and local requirements.
Calculation inputs
- Ventilation scenario
- Residence · ASHRAE 62.2 example
- Volume unit
- Cubic feet (ft³)
- Room or dwelling volume
- 12000 ft³
- Target air changes per hour
- 0.35 ACH
- Dwelling floor area
- 1500 ft²
- Dwelling bedrooms
- 3
- Existing outdoor air
- 0 CFM
- Existing particle clean-air delivery
- 0 CFM CADR
Worked example
For a 1,500 ft², three-bedroom home with 8 ft ceilings, compare a 0.35 ACH example with the whole-dwelling outdoor airflow estimate. An ERV supplies and exhausts a balanced airflow, measured once for air changes.
Outdoor-only fan or ERV target 75 CFM
Formulas and assumptions
- Air exchange
- CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
- Whole-dwelling baseline
- 62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
- Outdoor flow and filtered air
- Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.
Frequently asked questions
Can a HEPA air cleaner meet an outdoor ventilation requirement?
Particle CADR adds equivalent clean air for particles. An outdoor flow requirement still calls for outdoor air. Source exhaust controls moisture, smoke and gases near their source.
How should I count balanced ERV air in ACH?
Use the delivered outdoor supply for a balanced ERV. The paired exhaust flow is the same air exchange, so count it once.
Do the ventilation presets establish a code-compliant airflow?
Use the scenario values for screening. Check the locally adopted standard, occupancy, system operation and measured airflow for the installed system.