Air Changes per Hour (ACH) & CFM Calculator

Convert room volume and target ACH to CFM. Compare outdoor exhaust or ERV airflow with particle CADR for rooms, homes and classrooms.

Room and air changes

Floor area × average ceiling height, in the unit selected above.

Scenario values are editable planning examples.

Enter 0 for a studio. The baseline uses a minimum of one bedroom.

Measured air and filtration

Use delivered outdoor supply or exhaust. Count balanced airflow once.

Results

Example estimate
Outdoor-only fan or ERV target75 CFM
ACH airflow target 70 CFM Scenario outdoor baseline 75 CFM Existing outdoor airflow 0 CFM Added HEPA CADR 0 CFM
Added filtration assumes the outdoor baseline is met first.
Room volume
12,000 ft³
Room volume in metric
339.8 m³
Flow for target ACH
70 CFM
Scenario outdoor baseline
75 CFM
Added outdoor airflow for full ACH
75 CFM
Outdoor baseline still needed
75 CFM
Added particle CADR after baseline
0 CFM CADR
Existing outdoor ACH
0 ACH
Existing particle clean-air ACH
0 eACH
  • The whole-dwelling example uses the 62.2 base flow before infiltration credits and other adjustments. Confirm the adopted edition and local requirements.

Worked example

For a 1,500 ft², three-bedroom home with 8 ft ceilings, compare a 0.35 ACH example with the whole-dwelling outdoor airflow estimate. An ERV supplies and exhausts a balanced airflow, measured once for air changes.

Outdoor-only fan or ERV target 75 CFM

Formulas and assumptions

Air exchange
CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
Whole-dwelling baseline
62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
Outdoor flow and filtered air
Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.

Frequently asked questions

Can a HEPA air cleaner meet an outdoor ventilation requirement?

Particle CADR adds equivalent clean air for particles. An outdoor flow requirement still calls for outdoor air. Source exhaust controls moisture, smoke and gases near their source.

How should I count balanced ERV air in ACH?

Use the delivered outdoor supply for a balanced ERV. The paired exhaust flow is the same air exchange, so count it once.

Do the ventilation presets establish a code-compliant airflow?

Use the scenario values for screening. Check the locally adopted standard, occupancy, system operation and measured airflow for the installed system.

Sizing guides