400 CFM Round Duct Size at Low Static Pressure

Find a round duct for 400 CFM with a 0.07 in. w.c./100 ft friction target and a 700 FPM velocity ceiling.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

0.06–0.12 is a comparison range. Use the project’s actual friction budget.

Results

Example estimate
Round internal diameter11 in
Ø 11 in 12 × 8 in Round velocity 606 / 700 FPM Rectangular velocity 600 / 700 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
12 × 8 in
Rectangular equivalent diameter
10.66 in
Target friction
0.07 in. w.c./100 ft
Round friction
0.0537 in. w.c./100 ft
Rectangular friction
0.0627 in. w.c./100 ft
Friction-only round minimum
10.42 in
Velocity-only round minimum
10.24 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

A 400 CFM branch may be sized by noise before it is sized by friction. Compare the unrounded minimum diameter for each constraint to see why the whole-inch recommendation rounds up.

Round internal diameter 11 in

What to check next

Check the branch takeoff and register pressure drop. A low-velocity duct can still be noisy at a small grille or a sharp transition.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

Can an 8-inch duct move 400 CFM quietly?

At 400 CFM the average speed in an 8-inch round duct is about 1,146 FPM. Compare that with the branch velocity target and the terminal’s own sound data.

Does a common 400 CFM per ton rule specify a branch airflow?

Equipment airflow is a system setting. Use a room-by-room flow schedule to allocate the actual CFM to each branch.