1,200 CFM Round Duct With a 0.06 Friction Target

Compare a 1,200 CFM supply run at a tight 0.06 in. w.c./100 ft budget and an 850 FPM velocity limit.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

0.06–0.12 is a comparison range. Use the project’s actual friction budget.

Results

Example estimate
Round internal diameter17 in
Ø 17 in 19 × 12 in Round velocity 761 / 850 FPM Rectangular velocity 758 / 850 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
19 × 12 in
Rectangular equivalent diameter
16.4 in
Target friction
0.06 in. w.c./100 ft
Round friction
0.0478 in. w.c./100 ft
Rectangular friction
0.057 in. w.c./100 ft
Friction-only round minimum
16.23 in
Velocity-only round minimum
16.09 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

This straight-duct example starts at the low end of the friction comparison range. Raise the target to 0.10 and compare how the modeled friction minimum and final rounded diameter move.

Round internal diameter 17 in

What to check next

If the project has a long effective run, enter its remaining static pressure and total effective length. Confirm the blower can deliver 1,200 CFM at the resulting system pressure.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

Does a lower friction budget always make the 1,200 CFM size larger?

It raises the friction-based minimum. The rounded final size can stay the same when the velocity limit is already more restrictive.

Can 1,200 CFM use the diameter stamped on an insulated flex jacket?

Use the inner duct diameter. The jacket describes the outside of the insulated assembly and can be much larger.

More sizing examples

Open the general duct sizing calculator