Duct Size, CFM & Friction Rate Calculator
Size round and rectangular ducts from CFM, material, friction rate and a velocity limit. Compare dimensions using Manual D duct design principles.
Inputs
Results ↓Results
Example estimate- Rectangular internal size
- 21 × 10 in
- Rectangular equivalent diameter
- 15.58 in
- Target friction
- 0.08 in. w.c./100 ft
- Round friction
- 0.0643 in. w.c./100 ft
- Rectangular friction
- 0.0734 in. w.c./100 ft
- Friction-only round minimum
- 15.31 in
- Velocity-only round minimum
- 15.64 in
- Round material
- Galvanized steel
- Rectangular material
- Galvanized steel
Calculation inputs
- Design airflow
- 1200 CFM
- Duct material
- Galvanized steel
- Rectangular short side
- 10 in
- Air velocity limit
- 900 FPM
- Friction rate source
- Enter target friction rate
- Target friction rate
- 0.08 in. w.c./100 ft
Worked example
Start with a 1,200 CFM steel supply trunk, a 0.08 in. w.c./100 ft target and 10 inches of available rectangular height. Compare the resulting air velocity using each shape’s real cross-sectional area.
Round internal diameter 16 in
Formulas and assumptions
- Pressure budget
- Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
- Straight duct loss
- The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
- Rectangular equivalent
- Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.
Frequently asked questions
Is 0.08 inches of water per 100 feet a universal duct friction rate?
Use the fan pressure left after filters, coils and other components, then divide by the design path’s total effective length. A standard comparison value can be useful before those measurements are available.
Why does equal-friction rectangular duct have a different velocity?
An equal-friction dimension compares flow resistance. Air velocity divides the same CFM by each duct’s physical area, which differs between the shapes.
Does this duct calculator include transitions and elbows?
Include the fittings in total effective length when finding the friction budget. Review fitting losses, deformation, sound and actual static pressure separately for final design.
Sizing guides
- 400 CFM Round Duct Size at Low Static Pressure
- 600 CFM Flex Duct Size and Friction
- 800 CFM Rectangular Duct for an 8-Inch Cavity
- 1,000 CFM Round Duct and Noise Check
- 1,200 CFM Round Duct With a 0.06 Friction Target
- 1,600 CFM Rectangular Duct for a Supply Run
- 2,000 CFM Round vs. Rectangular Duct Size
- 3-Ton AC Supply Trunk Duct at 1,200 CFM
- 4-Ton AC Trunk Duct at 1,600 CFM
- 5-Ton AC Main Duct at 2,000 CFM