PEX Tubing Length for a 1,000 ft² Radiant Floor
Calculate tubing footage, loop length and manifold ports for a 1,000 ft² radiant floor at 8-inch spacing.
Inputs
Results ↓Results
Example estimateTotal tubing including tails1,710 ft
- Balanced loop length
- 285 ft
- Balanced circuits
- 6 loops
- Manifold supply/return pairs
- 6 ports
- Active tubing before tails
- 1,590 ft
- Supply and return tails per loop
- 20 ft
- Design floor load
- 24,000 BTU/h
- Total manifold flow
- 3.2 GPM
- Flow per loop
- 0.53 GPM
- Modeled tubing velocity
- 0.97 ft/s
- Tubing and assumed ID
- PEX-A · 0.475 in ID
- Verify tubing ID, bend radius, oxygen barrier, floor output and pump head for the installed system.
Calculation inputs
- Net heated floor area
- 1000 ft²
- Tube spacing on center
- 8 in
- Nominal tubing size
- ½ in
- PEX type
- PEX-A
- Routing allowance
- 6 %
- Manifold distance per circuit
- 10 ft
- Maximum total circuit length
- 300 ft
- Design floor heat load
- 24 BTU/h·ft²
- Supply-to-return temperature drop
- 15 °F
Worked example
The net tubing area is 1,000 ft² at 8 inches on center. Add six percent routing allowance and a 10 ft one-way run to each loop, then check the resulting footage against coil sizes.
Total tubing including tails 1,710 ft
What to check next
Draw each loop with its own tail length before ordering. Account for separate pours, exterior perimeter zones and the manifold’s practical location.
Formulas and assumptions
- Active tube
- Active footage = floor area × 12 ÷ spacing in inches × (1 + routing allowance).
- Balanced circuits
- Circuit count = round up(active footage ÷ (loop limit − two manifold tails)). Balanced length = active footage ÷ circuits + tails.
- Water flow
- GPM = BTU/h ÷ (500 × supply-return ΔT). Divide system flow by the number of equally loaded circuits. The velocity uses representative tubing ID.
Frequently asked questions
How much active tube per square foot does 8-inch radiant spacing use?
The straight-layout starting point is 12 ÷ 8, or 1.5 linear ft per heated square foot. Add bends and tails for the installed length.
Should I count floor under a kitchen island in the 1,000 ft²?
Subtract the island or any other area omitted from the tubing layout. Verify the remaining active floor can deliver the room heat load.