Radiant PEX Loops for a 2,000 ft² Slab
Work out circuit count, manifold capacity and water flow for 2,000 heated square feet using 12-inch PEX spacing.
Inputs
Results ↓Results
Example estimateTotal tubing including tails2,388 ft
- Balanced loop length
- 298.5 ft
- Balanced circuits
- 8 loops
- Manifold supply/return pairs
- 8 ports
- Active tubing before tails
- 2,100 ft
- Supply and return tails per loop
- 36 ft
- Design floor load
- 38,000 BTU/h
- Total manifold flow
- 5.07 GPM
- Flow per loop
- 0.63 GPM
- Modeled tubing velocity
- 0.79 ft/s
- Tubing and assumed ID
- PEX-A · 0.574 in ID
- Verify tubing ID, bend radius, oxygen barrier, floor output and pump head for the installed system.
Calculation inputs
- Net heated floor area
- 2000 ft²
- Tube spacing on center
- 12 in
- Nominal tubing size
- ⅝ in
- PEX type
- PEX-A
- Routing allowance
- 5 %
- Manifold distance per circuit
- 18 ft
- Maximum total circuit length
- 300 ft
- Design floor heat load
- 19 BTU/h·ft²
- Supply-to-return temperature drop
- 15 °F
Worked example
The slab uses 12-inch spacing with 18 ft manifold leads. Divide the active length among equal circuits so the full route of each stays within 300 ft.
Total tubing including tails 2,388 ft
What to check next
Consider two manifold locations if the slab has distant wings or distinctly different loads. Shorter tails can reduce both tube footage and pump pressure.
Formulas and assumptions
- Active tube
- Active footage = floor area × 12 ÷ spacing in inches × (1 + routing allowance).
- Balanced circuits
- Circuit count = round up(active footage ÷ (loop limit − two manifold tails)). Balanced length = active footage ÷ circuits + tails.
- Water flow
- GPM = BTU/h ÷ (500 × supply-return ΔT). Divide system flow by the number of equally loaded circuits. The velocity uses representative tubing ID.
Frequently asked questions
How many ports does a radiant manifold need for the 2,000 ft² example?
Use one supply-and-return port pair per calculated circuit. Split into multiple manifolds if measured leads or zoning require it.
Could 12-inch spacing be too wide in parts of a large slab?
Perimeter exposure, floor coverings and water temperature can require tighter spacing in some zones. Confirm output and surface temperature for the design.