Radiant PEX Loops for a 2,000 ft² Slab

Work out circuit count, manifold capacity and water flow for 2,000 heated square feet using 12-inch PEX spacing.

Heated surface and tubing

Subtract walls, fixed cabinets and other areas without active tube.

Adds footage for turns and layout variation.

Manifold and heat load

Enter the one-way distance. The model adds supply and return tails.

Includes both tails. Use a lower limit when the hydraulic design calls for it.

Results

Example estimate
Total tubing including tails2,388 ft
SupplyReturn 262.5 ft active per loop
One circuit shown. Supply and return tails are included in the balanced loop length.
Balanced loop length
298.5 ft
Balanced circuits
8 loops
Manifold supply/return pairs
8 ports
Active tubing before tails
2,100 ft
Supply and return tails per loop
36 ft
Design floor load
38,000 BTU/h
Total manifold flow
5.07 GPM
Flow per loop
0.63 GPM
Modeled tubing velocity
0.79 ft/s
Tubing and assumed ID
PEX-A · 0.574 in ID
  • Verify tubing ID, bend radius, oxygen barrier, floor output and pump head for the installed system.

Worked example

The slab uses 12-inch spacing with 18 ft manifold leads. Divide the active length among equal circuits so the full route of each stays within 300 ft.

Total tubing including tails 2,388 ft

What to check next

Consider two manifold locations if the slab has distant wings or distinctly different loads. Shorter tails can reduce both tube footage and pump pressure.

Formulas and assumptions

Active tube
Active footage = floor area × 12 ÷ spacing in inches × (1 + routing allowance).
Balanced circuits
Circuit count = round up(active footage ÷ (loop limit − two manifold tails)). Balanced length = active footage ÷ circuits + tails.
Water flow
GPM = BTU/h ÷ (500 × supply-return ΔT). Divide system flow by the number of equally loaded circuits. The velocity uses representative tubing ID.

Frequently asked questions

How many ports does a radiant manifold need for the 2,000 ft² example?

Use one supply-and-return port pair per calculated circuit. Split into multiple manifolds if measured leads or zoning require it.

Could 12-inch spacing be too wide in parts of a large slab?

Perimeter exposure, floor coverings and water temperature can require tighter spacing in some zones. Confirm output and surface temperature for the design.