PEX Footage at 6-Inch Radiant Spacing
Estimate tubing demand in a 480 ft² perimeter zone at 6 inches on center and compare it with wider spacing.
Inputs
Results ↓Results
Example estimateTotal tubing including tails1,100.8 ft
- Balanced loop length
- 275.2 ft
- Balanced circuits
- 4 loops
- Manifold supply/return pairs
- 4 ports
- Active tubing before tails
- 1,036.8 ft
- Supply and return tails per loop
- 16 ft
- Design floor load
- 14,880 BTU/h
- Total manifold flow
- 2.48 GPM
- Flow per loop
- 0.62 GPM
- Modeled tubing velocity
- 1.12 ft/s
- Tubing and assumed ID
- PEX-A · 0.475 in ID
- Verify tubing ID, bend radius, oxygen barrier, floor output and pump head for the installed system.
Calculation inputs
- Net heated floor area
- 480 ft²
- Tube spacing on center
- 6 in
- Nominal tubing size
- ½ in
- PEX type
- PEX-A
- Routing allowance
- 8 %
- Manifold distance per circuit
- 8 ft
- Maximum total circuit length
- 300 ft
- Design floor heat load
- 31 BTU/h·ft²
- Supply-to-return temperature drop
- 12 °F
Worked example
A closely spaced 480 ft² zone uses about two feet of active tubing per square foot before routing. Change to 9 inches to compare circuit count and manifold demand.
Total tubing including tails 1,100.8 ft
What to check next
Use the tubing manufacturer’s minimum bend radius to plan turns at tight spacing. Mark obstruction zones and avoid compressing the tubing path at doors and control joints.
Formulas and assumptions
- Active tube
- Active footage = floor area × 12 ÷ spacing in inches × (1 + routing allowance).
- Balanced circuits
- Circuit count = round up(active footage ÷ (loop limit − two manifold tails)). Balanced length = active footage ÷ circuits + tails.
- Water flow
- GPM = BTU/h ÷ (500 × supply-return ΔT). Divide system flow by the number of equally loaded circuits. The velocity uses representative tubing ID.
Frequently asked questions
Why can 6-inch radiant spacing require another circuit?
Closer spacing adds active footage. More circuits keep combined tubing and tails within the chosen circuit limit.
Does halving radiant tube spacing double the floor’s heat output?
Heat output also depends on water temperature, floor assembly and room temperature. The tubing length changes directly with spacing in this layout estimate.