12,000 BTU Mini-Split for a Sunny Bedroom

See when afternoon glazing can push a sunny 430 ft² bedroom into the 12,000 BTU cooling class and how shading changes the estimate.

Room and use
Envelope and glazing

50% is two sides of a square room.

Use 0 if a conditioned space is above.

Use 0 to omit floor loss. Slab edges need separate modeling.

Use the whole-window rating in Btu/(h·ft²·°F).

Use natural air changes, not ACH50 from a blower-door test.

Weather and equipment

Sets example weather. Use local design temperatures when available.

Results

Example estimate
Suggested nominal class12,000 BTU/h
Cooling11,600 BTU/h 753.6 BTU/h0 BTU/h8,561.8 BTU/h1,080.6 BTU/h1,204 BTU/hHeating3,256 BTU/h 890.5 BTU/h0 BTU/h1,552.5 BTU/h812.7 BTU/h0 BTU/h
Each bar uses the same BTU/h scale.
  • Walls and ceiling · 754 cool / 890 heat
  • Exposed floor · 0 cool / 0 heat
  • Windows and sun · 8,562 cool / 1,553 heat
  • Outdoor air leakage · 1,081 cool / 813 heat
  • People and equipment · 1,204 cool / 0 heat
Modeled cooling load
11,600 BTU/h
Modeled heating loss
3,255.7 BTU/h
Cooling load in tons
0.97 tons
Minimum nominal capacity
11,600 BTU/h
Cold-weather capacity
98.8 % of nominal
Heating output at design
11,860 BTU/h
Summer / winter design
96°F / 40°F
Modeled outdoor leakage
25.1 CFM

Worked example

The example represents a large bedroom with afternoon sun on 115 ft² of glass. Change the window exposure from west to mostly shaded to see how much of the capacity requirement comes from the glazing.

Suggested nominal class 12,000 BTU/h

What to check next

Estimate the night-time load separately. A unit that fits afternoon peak sun can short-cycle overnight if its minimum output is high.

Formulas and assumptions

Envelope load
BTU/h = Σ(area × ΔT ÷ effective R) + window area × U × ΔT. Exposed ceilings add a 10°F summer solar allowance.
Air and internal gains
Leakage CFM = room volume × ACH ÷ 60. Sensible airflow load uses 1.08 × CFM × ΔT. Cooling also includes 0.68 × CFM × the zone moisture difference in grains, window solar gain, people and equipment.
Capacity and tons
Cooling tons = cooling BTU/h ÷ 12,000. For heating, divide design heat loss by the capacity ratio. Size up to the first listed nominal class that meets the selected load.

Frequently asked questions

Why might a sunny bedroom need 12k even with good wall insulation?

Direct solar gain can be larger than the heat that passes through opaque walls. Glazing area, shade and orientation affect the afternoon peak.

What should I check before putting a 12k head next to a bed?

Check minimum output, low fan speed, sound data and the airflow path. Keep the discharge away from the pillow area where possible.