Mini-Split BTU & Tonnage Calculator

Estimate room cooling and heating loads in BTU/h, choose a mini-split capacity class, and check cold-climate capacity before comparing models.

Room and use
Envelope and glazing

50% is two sides of a square room.

Use 0 if a conditioned space is above.

Use 0 to omit floor loss. Slab edges need separate modeling.

Use the whole-window rating in Btu/(h·ft²·°F).

Use natural air changes, not ACH50 from a blower-door test.

Weather and equipment

Sets example weather. Use local design temperatures when available.

Results

Example estimate
Suggested nominal class12,000 BTU/h
Cooling11,374 BTU/h 893.4 BTU/h0 BTU/h7,175 BTU/h1,535.8 BTU/h1,770 BTU/hHeating8,674 BTU/h 2,681 BTU/h0 BTU/h2,610 BTU/h3,382.6 BTU/h0 BTU/h
Each bar uses the same BTU/h scale.
  • Walls and ceiling · 893 cool / 2,681 heat
  • Exposed floor · 0 cool / 0 heat
  • Windows and sun · 7,175 cool / 2,610 heat
  • Outdoor air leakage · 1,536 cool / 3,383 heat
  • People and equipment · 1,770 cool / 0 heat
Modeled cooling load
11,374.1 BTU/h
Modeled heating loss
8,673.5 BTU/h
Cooling load in tons
0.95 tons
Minimum nominal capacity
11,374.1 BTU/h
Cold-weather capacity
92.1 % of nominal
Heating output at design
11,050 BTU/h
Summer / winter design
90°F / 12°F
Modeled outdoor leakage
54 CFM
  • The capacity curve is illustrative. Verify delivered heating capacity and operating limits for the exact model.

Worked example

Compare a 600 ft² room with 9 ft ceilings and 100 ft² of west-facing glass in a mixed climate. The glass area and exposure affect cooling, while the outdoor design temperature affects heating capacity.

Suggested nominal class 12,000 BTU/h

Formulas and assumptions

Envelope load
BTU/h = Σ(area × ΔT ÷ effective R) + window area × U × ΔT. Exposed ceilings add a 10°F summer solar allowance.
Air and internal gains
Leakage CFM = room volume × ACH ÷ 60. Sensible airflow load uses 1.08 × CFM × ΔT. Cooling also includes 0.68 × CFM × the zone moisture difference in grains, window solar gain, people and equipment.
Capacity and tons
Cooling tons = cooling BTU/h ÷ 12,000. For heating, divide design heat loss by the capacity ratio. Size up to the first listed nominal class that meets the selected load.

Frequently asked questions

How does the mini-split calculator account for a high ceiling?

Ceiling height increases exterior wall area and indoor air volume, so it changes transmission and leakage loads. The footprint uses a square-room approximation.

Which mini-split capacity should I check at the winter design temperature?

Use the delivered heating capacity for the exact outdoor and indoor unit combination. Compare it with the building heat loss at the same outdoor temperature.

When should I get a room-by-room Manual J calculation?

Use a full load calculation for final equipment selection, irregular layouts, large window areas, major envelope upgrades and permitting. The estimate here supports early comparisons.

Sizing guides