Mini-Split BTU & Tonnage Calculator
Estimate room cooling and heating loads in BTU/h, choose a mini-split capacity class, and check cold-climate capacity before comparing models.
Inputs
Results ↓Results
Example estimate- Walls and ceiling · 893 cool / 2,681 heat
- Exposed floor · 0 cool / 0 heat
- Windows and sun · 7,175 cool / 2,610 heat
- Outdoor air leakage · 1,536 cool / 3,383 heat
- People and equipment · 1,770 cool / 0 heat
- Modeled cooling load
- 11,374.1 BTU/h
- Modeled heating loss
- 8,673.5 BTU/h
- Cooling load in tons
- 0.95 tons
- Minimum nominal capacity
- 11,374.1 BTU/h
- Cold-weather capacity
- 92.1 % of nominal
- Heating output at design
- 11,050 BTU/h
- Summer / winter design
- 90°F / 12°F
- Modeled outdoor leakage
- 54 CFM
- The capacity curve is illustrative. Verify delivered heating capacity and operating limits for the exact model.
Calculation inputs
- Floor area
- 600 ft²
- Ceiling height
- 9 ft
- People in the room
- 3
- Room type
- Standard room
- Size for
- Heating and cooling
- Wall perimeter facing outdoors
- 50 %
- Effective wall R-value
- 13
- Effective ceiling R-value
- 30
- Effective exposed floor R-value
- 0
- Exterior window area
- 100 ft²
- Window U-factor
- 0.45
- Main window exposure
- West
- Estimated outdoor air leakage
- 0.6 ACH
- Illustrative climate zone
- 4 · Mixed
- Design temperature source
- Climate zone example
- Low-temperature capacity
- Cold-climate inverter curve
Worked example
Compare a 600 ft² room with 9 ft ceilings and 100 ft² of west-facing glass in a mixed climate. The glass area and exposure affect cooling, while the outdoor design temperature affects heating capacity.
Suggested nominal class 12,000 BTU/h
Formulas and assumptions
- Envelope load
- BTU/h = Σ(area × ΔT ÷ effective R) + window area × U × ΔT. Exposed ceilings add a 10°F summer solar allowance.
- Air and internal gains
- Leakage CFM = room volume × ACH ÷ 60. Sensible airflow load uses 1.08 × CFM × ΔT. Cooling also includes 0.68 × CFM × the zone moisture difference in grains, window solar gain, people and equipment.
- Capacity and tons
- Cooling tons = cooling BTU/h ÷ 12,000. For heating, divide design heat loss by the capacity ratio. Size up to the first listed nominal class that meets the selected load.
Frequently asked questions
How does the mini-split calculator account for a high ceiling?
Ceiling height increases exterior wall area and indoor air volume, so it changes transmission and leakage loads. The footprint uses a square-room approximation.
Which mini-split capacity should I check at the winter design temperature?
Use the delivered heating capacity for the exact outdoor and indoor unit combination. Compare it with the building heat loss at the same outdoor temperature.
When should I get a room-by-room Manual J calculation?
Use a full load calculation for final equipment selection, irregular layouts, large window areas, major envelope upgrades and permitting. The estimate here supports early comparisons.
Sizing guides
- 12,000 BTU Mini-Split for a One-Car Garage
- 18,000 BTU Mini-Split for a Two-Car Garage
- 24,000 BTU Mini-Split for a Large Garage
- 12,000 BTU Mini-Split for a Sunny Bedroom
- 18,000 BTU Mini-Split for a Loft Bedroom
- 24,000 BTU Mini-Split for a Large Bedroom Suite
- Mini-Split Size for a West-Facing Sunroom
- Cold-Climate Mini-Split Capacity at −10°F