24,000 BTU Mini-Split for a Large Garage
Test a 24,000 BTU mini-split for an 850 ft² insulated garage with 10 ft ceilings and a 0°F winter design example.
Inputs
Results ↓Results
Example estimate- Walls and ceiling · 1,757 cool / 7,150 heat
- Exposed floor · 0 cool / 0 heat
- Windows and sun · 2,822 cool / 1,733 heat
- Outdoor air leakage · 3,298 cool / 10,710 heat
- People and equipment · 1,540 cool / 0 heat
- Modeled cooling load
- 9,416.4 BTU/h
- Modeled heating loss
- 19,592.4 BTU/h
- Cooling load in tons
- 0.78 tons
- Minimum nominal capacity
- 23,448.4 BTU/h
- Cold-weather capacity
- 83.6 % of nominal
- Heating output at design
- 20,053.3 BTU/h
- Summer / winter design
- 89°F / 0°F
- Modeled outdoor leakage
- 141.7 CFM
- The capacity curve is illustrative. Verify delivered heating capacity and operating limits for the exact model.
Calculation inputs
- Floor area
- 850 ft²
- Ceiling height
- 10 ft
- People in the room
- 2
- Room type
- Standard room
- Size for
- Heating and cooling
- Wall perimeter facing outdoors
- 100 %
- Effective wall R-value
- 16
- Effective ceiling R-value
- 26
- Effective exposed floor R-value
- 0
- Exterior window area
- 55 ft²
- Window U-factor
- 0.45
- Main window exposure
- South
- Estimated outdoor air leakage
- 1 ACH
- Illustrative climate zone
- 5 · Cool
- Design temperature source
- Climate zone example
- Low-temperature capacity
- Cold-climate inverter curve
Worked example
An 850 ft² detached bay with a reasonably insulated shell can still need nearly the full 24k class on a subfreezing day. The estimate accounts for a cold-climate unit delivering less heat at 0°F than its nominal class.
Suggested nominal class 24,000 BTU/h
What to check next
Compare the supplier’s 0°F capacity with the calculated room heat loss. Consider separate zones if a shop partition or parked vehicles block air circulation.
Formulas and assumptions
- Envelope load
- BTU/h = Σ(area × ΔT ÷ effective R) + window area × U × ΔT. Exposed ceilings add a 10°F summer solar allowance.
- Air and internal gains
- Leakage CFM = room volume × ACH ÷ 60. Sensible airflow load uses 1.08 × CFM × ΔT. Cooling also includes 0.68 × CFM × the zone moisture difference in grains, window solar gain, people and equipment.
- Capacity and tons
- Cooling tons = cooling BTU/h ÷ 12,000. For heating, divide design heat loss by the capacity ratio. Size up to the first listed nominal class that meets the selected load.
Frequently asked questions
Does a 2-ton garage mini-split deliver 24,000 BTU/h at 0°F?
Use the performance table for the specific unit. Two tons describes a nominal cooling class and each unit has its own heating capacity at 0°F.
Which input is worth checking first in a large insulated garage?
Measure exterior dimensions and identify overhead-door and air-sealing weaknesses. Outdoor air leakage can dominate the load even with higher wall R-values.