1,600 CFM Rectangular Duct for a Supply Run

Estimate a rectangular supply duct for 1,600 CFM at 12 inches of available height, with a friction and velocity check.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

0.06–0.12 is a comparison range. Use the project’s actual friction budget.

Results

Example estimate
Round internal diameter19 in
Ø 19 in 22 × 12 in Round velocity 813 / 900 FPM Rectangular velocity 873 / 900 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
22 × 12 in
Rectangular equivalent diameter
17.56 in
Target friction
0.09 in. w.c./100 ft
Round friction
0.0471 in. w.c./100 ft
Rectangular friction
0.0693 in. w.c./100 ft
Friction-only round minimum
16.65 in
Velocity-only round minimum
18.05 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

The candidate uses a 12-inch internal short side. Read the resulting width and verify the aspect ratio before comparing sheet-metal layouts.

Round internal diameter 19 in

What to check next

Check access around a wide trunk for framing, hangers and service. Space downstream and branch takeoffs can determine a better trunk shape.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

Would a 12 × 20 duct keep 1,600 CFM below 900 FPM?

Its gross internal area is 240 square inches, so 1,600 CFM would pass at about 960 FPM. A wider or taller section lowers airspeed.

Where should the 1,600 CFM flow apply along a tapered trunk?

Use the full flow upstream of the first branch. Recalculate successive segments after subtracting each branch’s design flow.

More sizing examples

Open the general duct sizing calculator