2,000 CFM Round vs. Rectangular Duct Size

Compare round and 14-inch-height rectangular duct dimensions for 2,000 CFM and a 1,000 FPM main-trunk target.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

0.06–0.12 is a comparison range. Use the project’s actual friction budget.

Results

Example estimate
Round internal diameter20 in
Ø 20 in 21 × 14 in Round velocity 917 / 1,000 FPM Rectangular velocity 980 / 1,000 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
21 × 14 in
Rectangular equivalent diameter
18.65 in
Target friction
0.08 in. w.c./100 ft
Round friction
0.0553 in. w.c./100 ft
Rectangular friction
0.0779 in. w.c./100 ft
Friction-only round minimum
18.55 in
Velocity-only round minimum
19.15 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

A main duct carrying 2,000 CFM makes the tradeoff between round diameter and rectangular width easy to see. The two choices satisfy the same targets, but their actual velocities depend on different areas.

Round internal diameter 20 in

What to check next

Check where a large transition, balancing damper or return grille will fit. Model each path’s effective length and remaining pressure before ordering ductwork.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

How much internal duct area does 2,000 CFM need at 1,000 FPM?

Airflow divided by velocity gives 2.0 square feet, or 288 square inches. Friction can require more area than this lower bound.

Can I split a 2,000 CFM main into two smaller ducts?

Use the airflow assigned to each path and model each path’s pressure losses. A balanced split depends on more than total cross-sectional area.

More sizing examples

Open the general duct sizing calculator