3-Ton AC Supply Trunk Duct at 1,200 CFM
Use a 3-ton AC airflow example and calculate supply-trunk friction from 0.18 in. w.c. available at 240 ft effective length.
Inputs
Results ↓Results
Example estimate- Rectangular internal size
- 24 × 9 in
- Rectangular equivalent diameter
- 15.61 in
- Target friction
- 0.075 in. w.c./100 ft
- Round friction
- 0.0643 in. w.c./100 ft
- Rectangular friction
- 0.0727 in. w.c./100 ft
- Friction-only round minimum
- 15.51 in
- Velocity-only round minimum
- 15.22 in
- Round material
- Galvanized steel
- Rectangular material
- Galvanized steel
Calculation inputs
- Design airflow
- 1200 CFM
- Duct material
- Galvanized steel
- Rectangular short side
- 9 in
- Air velocity limit
- 950 FPM
- Friction rate source
- Use static pressure and effective length
- Available static pressure
- 0.18 in. w.c.
- Total effective length
- 240 ft
Worked example
The 3-ton example starts at 1,200 CFM and derives friction from measured or estimated available pressure. The 240 ft design path includes the straight lengths and fitting equivalents.
Round internal diameter 16 in
What to check next
Replace 1,200 CFM with the flow the selected coil and blower actually need. Moisture removal and manufacturer airflow limits can alter the target for a nominal 3-ton system.
Formulas and assumptions
- Pressure budget
- Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
- Straight duct loss
- The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
- Rectangular equivalent
- Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.
Frequently asked questions
What if my 3-ton setup is set to 1,050 CFM for humidity control?
Enter 1,050 CFM and the actual friction budget. Confirm the selected airflow is permitted by the equipment and matches the load and sensible heat ratio.
Should a 3-ton supply trunk use the blower’s full external static rating?
Subtract the pressure drops for non-duct components within the equipment selection’s rating setup before assigning the remaining pressure to the duct path.