3-Ton AC Supply Trunk Duct at 1,200 CFM

Use a 3-ton AC airflow example and calculate supply-trunk friction from 0.18 in. w.c. available at 240 ft effective length.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

Use fan pressure remaining after non-duct losses.

Include straight runs and equivalent fitting lengths for the design path.

Results

Example estimate
Round internal diameter16 in
Ø 16 in 24 × 9 in Round velocity 859 / 950 FPM Rectangular velocity 800 / 950 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
24 × 9 in
Rectangular equivalent diameter
15.61 in
Target friction
0.075 in. w.c./100 ft
Round friction
0.0643 in. w.c./100 ft
Rectangular friction
0.0727 in. w.c./100 ft
Friction-only round minimum
15.51 in
Velocity-only round minimum
15.22 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

The 3-ton example starts at 1,200 CFM and derives friction from measured or estimated available pressure. The 240 ft design path includes the straight lengths and fitting equivalents.

Round internal diameter 16 in

What to check next

Replace 1,200 CFM with the flow the selected coil and blower actually need. Moisture removal and manufacturer airflow limits can alter the target for a nominal 3-ton system.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

What if my 3-ton setup is set to 1,050 CFM for humidity control?

Enter 1,050 CFM and the actual friction budget. Confirm the selected airflow is permitted by the equipment and matches the load and sensible heat ratio.

Should a 3-ton supply trunk use the blower’s full external static rating?

Subtract the pressure drops for non-duct components within the equipment selection’s rating setup before assigning the remaining pressure to the duct path.