4-Ton AC Trunk Duct at 1,600 CFM
Check a 4-ton AC main trunk with 1,600 CFM, 0.22 in. w.c. available static and 280 ft of total effective length.
Inputs
Results ↓Results
Example estimate- Rectangular internal size
- 24 × 11 in
- Rectangular equivalent diameter
- 17.44 in
- Target friction
- 0.0786 in. w.c./100 ft
- Round friction
- 0.0614 in. w.c./100 ft
- Rectangular friction
- 0.0718 in. w.c./100 ft
- Friction-only round minimum
- 17.12 in
- Velocity-only round minimum
- 16.71 in
- Round material
- Galvanized steel
- Rectangular material
- Galvanized steel
Calculation inputs
- Design airflow
- 1600 CFM
- Duct material
- Galvanized steel
- Rectangular short side
- 11 in
- Air velocity limit
- 1050 FPM
- Friction rate source
- Use static pressure and effective length
- Available static pressure
- 0.22 in. w.c.
- Total effective length
- 280 ft
Worked example
The nominal 4-ton setup uses 1,600 CFM as a starting point. A shallow 11-inch rectangular section competes with a round duct under the same calculated pressure budget.
Round internal diameter 18 in
What to check next
Measure actual external static pressure once the system is installed and compare it with the manufacturer’s airflow table. The trunk size is one part of that check.
Formulas and assumptions
- Pressure budget
- Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
- Straight duct loss
- The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
- Rectangular equivalent
- Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.
Frequently asked questions
Can I use a 4-ton trunk estimate for a multi-zone system?
At minimum, check the maximum equipment airflow and the smallest operating zone separately. Dampers and controls change the effective airflow path.
Does a 4-ton trunk determine the return grille area?
Use return grille free area, the desired face velocity and the product pressure-drop data. The main duct section does not determine grille behavior.