4-Ton AC Trunk Duct at 1,600 CFM

Check a 4-ton AC main trunk with 1,600 CFM, 0.22 in. w.c. available static and 280 ft of total effective length.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

Use fan pressure remaining after non-duct losses.

Include straight runs and equivalent fitting lengths for the design path.

Results

Example estimate
Round internal diameter18 in
Ø 18 in 24 × 11 in Round velocity 905 / 1,050 FPM Rectangular velocity 873 / 1,050 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
24 × 11 in
Rectangular equivalent diameter
17.44 in
Target friction
0.0786 in. w.c./100 ft
Round friction
0.0614 in. w.c./100 ft
Rectangular friction
0.0718 in. w.c./100 ft
Friction-only round minimum
17.12 in
Velocity-only round minimum
16.71 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

The nominal 4-ton setup uses 1,600 CFM as a starting point. A shallow 11-inch rectangular section competes with a round duct under the same calculated pressure budget.

Round internal diameter 18 in

What to check next

Measure actual external static pressure once the system is installed and compare it with the manufacturer’s airflow table. The trunk size is one part of that check.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

Can I use a 4-ton trunk estimate for a multi-zone system?

At minimum, check the maximum equipment airflow and the smallest operating zone separately. Dampers and controls change the effective airflow path.

Does a 4-ton trunk determine the return grille area?

Use return grille free area, the desired face velocity and the product pressure-drop data. The main duct section does not determine grille behavior.

More sizing examples

Open the general duct sizing calculator