5-Ton AC Main Duct at 2,000 CFM
Estimate a 5-ton AC trunk from 2,000 CFM and a 320 ft design path with 0.24 in. w.c. available static.
Inputs
Results ↓Results
Example estimate- Rectangular internal size
- 24 × 13 in
- Rectangular equivalent diameter
- 19.09 in
- Target friction
- 0.075 in. w.c./100 ft
- Round friction
- 0.0711 in. w.c./100 ft
- Rectangular friction
- 0.0695 in. w.c./100 ft
- Friction-only round minimum
- 18.79 in
- Velocity-only round minimum
- 18.26 in
- Round material
- Galvanized steel
- Rectangular material
- Galvanized steel
Calculation inputs
- Design airflow
- 2000 CFM
- Duct material
- Galvanized steel
- Rectangular short side
- 13 in
- Air velocity limit
- 1100 FPM
- Friction rate source
- Use static pressure and effective length
- Available static pressure
- 0.24 in. w.c.
- Total effective length
- 320 ft
Worked example
High flow and a longer design path make the pressure budget important in this 5-ton example. The selected 13-inch short dimension may require a wide profile or a deeper duct in a different route.
Round internal diameter 19 in
What to check next
Compare splitting the main near the air handler with running a single low-profile trunk. Include transition, branch and grille losses on each critical path.
Formulas and assumptions
- Pressure budget
- Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
- Straight duct loss
- The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
- Rectangular equivalent
- Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.
Frequently asked questions
Is 2,000 CFM automatic for all 5-ton AC systems?
It is a common comparison based on 400 CFM per ton. The equipment airflow table and design load set the value for the installed system.
Why can a 5-ton design require reworking the filter and return?
A high pressure drop on the return side reduces the pressure available to the supply ducts. Check filter area, return path and fan data together.