5-Ton AC Main Duct at 2,000 CFM

Estimate a 5-ton AC trunk from 2,000 CFM and a 320 ft design path with 0.24 in. w.c. available static.

Airflow and duct

For flex, the rectangular comparison uses galvanized steel.

A screening limit for noise. Match the run and grille design.

Friction budget

Use fan pressure remaining after non-duct losses.

Include straight runs and equivalent fitting lengths for the design path.

Results

Example estimate
Round internal diameter19 in
Ø 19 in 24 × 13 in Round velocity 1,016 / 1,100 FPM Rectangular velocity 923 / 1,100 FPM
Sections share a scale. Velocity uses each duct’s clear internal area.
Rectangular internal size
24 × 13 in
Rectangular equivalent diameter
19.09 in
Target friction
0.075 in. w.c./100 ft
Round friction
0.0711 in. w.c./100 ft
Rectangular friction
0.0695 in. w.c./100 ft
Friction-only round minimum
18.79 in
Velocity-only round minimum
18.26 in
Round material
Galvanized steel
Rectangular material
Galvanized steel

Worked example

High flow and a longer design path make the pressure budget important in this 5-ton example. The selected 13-inch short dimension may require a wide profile or a deeper duct in a different route.

Round internal diameter 19 in

What to check next

Compare splitting the main near the air handler with running a single low-profile trunk. Include transition, branch and grille losses on each critical path.

Formulas and assumptions

Pressure budget
Design friction rate = 100 × available static pressure ÷ total effective length. Include fitting equivalent length on the critical path.
Straight duct loss
The round size uses Darcy–Weisbach with Colebrook friction, standard air density and representative roughness. The candidate rounds up to whole-inch internal dimensions.
Rectangular equivalent
Equivalent round diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Velocity uses the real cross section. The comparison limits the aspect ratio to 4:1.

Frequently asked questions

Is 2,000 CFM automatic for all 5-ton AC systems?

It is a common comparison based on 400 CFM per ton. The equipment airflow table and design load set the value for the installed system.

Why can a 5-ton design require reworking the filter and return?

A high pressure drop on the return side reduces the pressure available to the supply ducts. Check filter area, return path and fan data together.