Dew Point at 75°F and 50% Relative Humidity
Find dew point, wet-bulb and humidity ratio at a common indoor state of 75°F and 50% RH.
Inputs
Results ↓Results
Example estimateEntering-air dew point55.1 °F
- Stull wet-bulb
- 62.7 °F
- Entering humidity ratio
- 64.5 gr/lb
- Entering enthalpy
- 28.08 BTU/lb dry air
- Leaving enthalpy
- 28.08 BTU/lb dry air
- Condensation at surface
- Above dew point
- Surface margin above dew point
- 1.9 °F
- Sensible load
- 0 BTU/h
- Latent load
- 0 BTU/h
- Total airside load
- 0 BTU/h
- Sensible heat ratio
- —
Calculation inputs
- Entering dry-bulb temperature
- 75 °F
- Entering relative humidity
- 50 %
- Cold surface temperature
- 57 °F
- Barometric pressure
- 101.325 kPa
- Leaving dry-bulb temperature
- 75 °F
- Leaving relative humidity
- 50 %
- Airflow at the entering condition
- 0 CFM
Worked example
For 75°F and 50% RH, the dew point is near 55°F. Compare a 57°F supply grille and a colder 52°F surface to see when the surface flag changes.
Entering-air dew point 55.1 °F
What to check next
If the room RH sensor sits near a thermostat, validate the air condition at the actual surface before using the reading for a condensation decision.
Formulas and assumptions
- Moist-air state
- A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
- Enthalpy and wet-bulb
- Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
- Airside heat transfer
- Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.
Frequently asked questions
How much moisture is in 75°F air at 50% RH?
Use humidity ratio in grains per pound of dry air. The mass ratio changes with barometric pressure even when temperature and RH are the same.
Do 75°F and 50% RH describe the same dew point as colder air at 50%?
At the same RH a colder air temperature has lower water-vapor pressure, so its dew point is lower.