Basement Dehumidifier Dew Point and Slab Condensation

Check whether a 58°F basement slab can condense moisture from 70°F air at 65% RH and compare a drier target.

Entering air and cold surface

Use the duct jacket, slab or pipe surface temperature.

Use local station pressure. 101.325 kPa is standard sea level.

Leaving air and airflow

Set to 0 if you only need the air properties.

Results

Example estimate
Entering-air dew point57.7 °F
Dew point57.7°F Surface58°F Wet-bulb62°F Dry-bulb70°F
The shaded range is at or below the entering-air dew point.
Stull wet-bulb
62 °F
Entering humidity ratio
70.9 gr/lb
Entering enthalpy
27.87 BTU/lb dry air
Leaving enthalpy
25.28 BTU/lb dry air
Condensation at surface
Above dew point
Surface margin above dew point
0.3 °F
Sensible load
0 BTU/h
Latent load
2,858 BTU/h
Total airside load
2,858 BTU/h
Sensible heat ratio
0

Worked example

The slab is cooler than the surrounding basement air. Compare its 58°F surface temperature with the modeled dew point and lower RH to see how much moisture margin changes.

Entering-air dew point 57.7 °F

What to check next

Measure near the slab and in cooler corners. Determine whether moisture comes from humid air, liquid water or vapor passing through the assembly before choosing a dehumidifier.

Formulas and assumptions

Moist-air state
A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
Enthalpy and wet-bulb
Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
Airside heat transfer
Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.

Frequently asked questions

Why does a basement floor look wet when the room air feels only slightly humid?

A cool slab can be below the air’s dew point while the air feels comfortable. Temperature and RH near the slab are more informative than RH upstairs.

Does lowering basement air to 50% RH always prevent floor condensation?

Check the coldest surface against the new dew point. A lower surface temperature or wetter local air can still cause condensation.

More sizing examples

Open the general dew point and sensible heat calculator