Sweating Duct Dew Point in a Humid Attic
Compare an attic duct jacket temperature with the air dew point at 88°F and 65% RH to assess sweating risk.
Inputs
Results ↓Results
Example estimate- Stull wet-bulb
- 78.5 °F
- Entering humidity ratio
- 129.9 gr/lb
- Entering enthalpy
- 41.53 BTU/lb dry air
- Leaving enthalpy
- 29.11 BTU/lb dry air
- Condensation at surface
- At or below dew point
- Surface margin above dew point
- -5.8 °F
- Sensible load
- 0 BTU/h
- Latent load
- 0 BTU/h
- Total airside load
- 0 BTU/h
- Sensible heat ratio
- —
Calculation inputs
- Entering dry-bulb temperature
- 88 °F
- Entering relative humidity
- 65 %
- Cold surface temperature
- 69 °F
- Barometric pressure
- 101.325 kPa
- Leaving dry-bulb temperature
- 75 °F
- Leaving relative humidity
- 55 %
- Airflow at the entering condition
- 0 CFM
Worked example
The duct jacket at 69°F sits in hot, humid attic air. The condensation decision uses the jacket’s surface temperature and the air around it. The airflow input is zero because this is a surface check.
Entering-air dew point 74.8 °F
What to check next
Inspect damaged vapor barriers, insulation gaps and cold spots near fittings. Measure the surface in steady operation, including the underside of the duct.
Formulas and assumptions
- Moist-air state
- A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
- Enthalpy and wet-bulb
- Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
- Airside heat transfer
- Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.
Frequently asked questions
Should I compare attic air dew point with the temperature of air inside the duct?
Use the temperature of the exposed duct jacket. Insulation can keep the jacket warmer than the air moving inside.
Why is duct sweating worse at seams and supports?
Compressed insulation, gaps or thermal bridges can lower local surface temperature. Inspect the coldest points as well as the middle of straight runs.