High-Altitude Air Enthalpy and Coil Load

Compare a psychrometric calculation at 83 kPa with a sea-level estimate using identical temperatures, humidity and CFM.

Entering air and cold surface

Use the duct jacket, slab or pipe surface temperature.

Use local station pressure. 101.325 kPa is standard sea level.

Leaving air and airflow

Set to 0 if you only need the air properties.

Results

Example estimate
Entering-air dew point55.3 °F
Dew point55.3°F Surface51°F Wet-bulb65.6°F Dry-bulb82°F
The shaded range is at or below the entering-air dew point.
Stull wet-bulb
65.6 °F
Entering humidity ratio
79.6 gr/lb
Entering enthalpy
32.16 BTU/lb dry air
Leaving enthalpy
25.48 BTU/lb dry air
Condensation at surface
At or below dew point
Surface margin above dew point
-4.3 °F
Sensible load
18,709 BTU/h
Latent load
2,527 BTU/h
Total airside load
21,235 BTU/h
Sensible heat ratio
0.881
  • The wet-bulb approximation uses sea-level pressure. Humidity ratio, enthalpy and load use the entered pressure.

Worked example

At 83 kPa the modeled dry-air mass per CFM is lower while humidity ratio at the same RH is higher. Change the pressure to 101.325 kPa and compare enthalpy, sensible load and latent load.

Entering-air dew point 55.3 °F

What to check next

Use local station pressure for this calculation and obtain a pressure-corrected wet-bulb value when it drives equipment selection. The Stull wet-bulb estimate remains near-sea-level.

Formulas and assumptions

Moist-air state
A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
Enthalpy and wet-bulb
Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
Airside heat transfer
Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.

Frequently asked questions

Does altitude directly change dew point at fixed dry-bulb and RH?

Under the water-vapor approximation, those two inputs fix vapor pressure and dew point. Pressure affects humidity ratio and air mass flow separately.

Can I enter sea-level-adjusted weather pressure for a mountain air handler?

Use actual station pressure where the air handler operates. Sea-level-adjusted pressure is for weather comparison and overstates the local air density.

More sizing examples

Open the general dew point and sensible heat calculator