High-Altitude Air Enthalpy and Coil Load
Compare a psychrometric calculation at 83 kPa with a sea-level estimate using identical temperatures, humidity and CFM.
Inputs
Results ↓Results
Example estimate- Stull wet-bulb
- 65.6 °F
- Entering humidity ratio
- 79.6 gr/lb
- Entering enthalpy
- 32.16 BTU/lb dry air
- Leaving enthalpy
- 25.48 BTU/lb dry air
- Condensation at surface
- At or below dew point
- Surface margin above dew point
- -4.3 °F
- Sensible load
- 18,709 BTU/h
- Latent load
- 2,527 BTU/h
- Total airside load
- 21,235 BTU/h
- Sensible heat ratio
- 0.881
- The wet-bulb approximation uses sea-level pressure. Humidity ratio, enthalpy and load use the entered pressure.
Calculation inputs
- Entering dry-bulb temperature
- 82 °F
- Entering relative humidity
- 40 %
- Cold surface temperature
- 51 °F
- Barometric pressure
- 83 kPa
- Leaving dry-bulb temperature
- 58 °F
- Leaving relative humidity
- 85 %
- Airflow at the entering condition
- 900 CFM
Worked example
At 83 kPa the modeled dry-air mass per CFM is lower while humidity ratio at the same RH is higher. Change the pressure to 101.325 kPa and compare enthalpy, sensible load and latent load.
Entering-air dew point 55.3 °F
What to check next
Use local station pressure for this calculation and obtain a pressure-corrected wet-bulb value when it drives equipment selection. The Stull wet-bulb estimate remains near-sea-level.
Formulas and assumptions
- Moist-air state
- A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
- Enthalpy and wet-bulb
- Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
- Airside heat transfer
- Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.
Frequently asked questions
Does altitude directly change dew point at fixed dry-bulb and RH?
Under the water-vapor approximation, those two inputs fix vapor pressure and dew point. Pressure affects humidity ratio and air mass flow separately.
Can I enter sea-level-adjusted weather pressure for a mountain air handler?
Use actual station pressure where the air handler operates. Sea-level-adjusted pressure is for weather comparison and overstates the local air density.