Air Handler Coil Sensible and Latent Load
Calculate airside sensible, latent and total BTU/h from 1,200 CFM and the entering and leaving air states.
Inputs
Results ↓Results
Example estimate- Stull wet-bulb
- 68.4 °F
- Entering humidity ratio
- 84.1 gr/lb
- Entering enthalpy
- 32.37 BTU/lb dry air
- Leaving enthalpy
- 22.66 BTU/lb dry air
- Condensation at surface
- At or below dew point
- Surface margin above dew point
- -14.4 °F
- Sensible load
- 31,843 BTU/h
- Latent load
- 18,580 BTU/h
- Total airside load
- 50,424 BTU/h
- Sensible heat ratio
- 0.632
Calculation inputs
- Entering dry-bulb temperature
- 80 °F
- Entering relative humidity
- 55 %
- Cold surface temperature
- 48 °F
- Barometric pressure
- 101.325 kPa
- Leaving dry-bulb temperature
- 55 °F
- Leaving relative humidity
- 95 %
- Airflow at the entering condition
- 1200 CFM
Worked example
Air at 80°F and 55% RH leaves the coil at 55°F and 95% RH. Because colder saturated air holds less moisture, the coil can remove water despite a higher leaving relative humidity.
Entering-air dew point 62.4 °F
What to check next
Use measured entering airflow and representative mixed-air readings. The model reports signed heat transfer, which is useful when a leaving-air target requires humidification or reheat.
Formulas and assumptions
- Moist-air state
- A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
- Enthalpy and wet-bulb
- Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
- Airside heat transfer
- Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.
Frequently asked questions
Why is the air handler’s leaving RH higher even if it removes moisture?
Relative humidity rises as air cools toward saturation. Compare humidity ratios to see whether the water mass per pound of dry air actually falls.
Can I estimate coil total capacity from entering and leaving dry-bulb only?
Dry-bulb change describes sensible cooling. Use humidity or wet-bulb data as well to find the enthalpy change and latent removal.