Air Handler Coil Sensible and Latent Load

Calculate airside sensible, latent and total BTU/h from 1,200 CFM and the entering and leaving air states.

Entering air and cold surface

Use the duct jacket, slab or pipe surface temperature.

Use local station pressure. 101.325 kPa is standard sea level.

Leaving air and airflow

Set to 0 if you only need the air properties.

Results

Example estimate
Entering-air dew point62.4 °F
Dew point62.4°F Surface48°F Wet-bulb68.4°F Dry-bulb80°F
The shaded range is at or below the entering-air dew point.
Stull wet-bulb
68.4 °F
Entering humidity ratio
84.1 gr/lb
Entering enthalpy
32.37 BTU/lb dry air
Leaving enthalpy
22.66 BTU/lb dry air
Condensation at surface
At or below dew point
Surface margin above dew point
-14.4 °F
Sensible load
31,843 BTU/h
Latent load
18,580 BTU/h
Total airside load
50,424 BTU/h
Sensible heat ratio
0.632

Worked example

Air at 80°F and 55% RH leaves the coil at 55°F and 95% RH. Because colder saturated air holds less moisture, the coil can remove water despite a higher leaving relative humidity.

Entering-air dew point 62.4 °F

What to check next

Use measured entering airflow and representative mixed-air readings. The model reports signed heat transfer, which is useful when a leaving-air target requires humidification or reheat.

Formulas and assumptions

Moist-air state
A Magnus water-vapor approximation gives dew point. Humidity ratio = 0.621945 × vapor pressure ÷ (barometric pressure − vapor pressure).
Enthalpy and wet-bulb
Enthalpy = 0.24 × °F + humidity ratio × (1061 + 0.444 × °F), in BTU/lb dry air. Stull estimates wet-bulb from dry-bulb and RH near standard pressure.
Airside heat transfer
Dry-air mass flow = 60 × CFM ÷ entering specific volume. Total BTU/h = mass flow × change in enthalpy. Sensible and latent components retain the sign of the transfer.

Frequently asked questions

Why is the air handler’s leaving RH higher even if it removes moisture?

Relative humidity rises as air cools toward saturation. Compare humidity ratios to see whether the water mass per pound of dry air actually falls.

Can I estimate coil total capacity from entering and leaving dry-bulb only?

Dry-bulb change describes sensible cooling. Use humidity or wet-bulb data as well to find the enthalpy change and latent removal.

More sizing examples

Open the general dew point and sensible heat calculator